Property
Description
Installation Tasks Guide. Note that the maximum number of
channels that may be used in a system is defined in the Experion
specification for that Experion release, This number is likely to be
less than the maximum number that can be configured in the
database as shown in "Adjusting sizing of non-licensed items."
Port properties for an ABB Totalflow channel
The Port tab defines the communication-related properties for a
channel. The properties vary according to the selected
Port Type
:
n
Serial
. This connection method is not fully supported for the
Experion system. Select this if you are using an RS-232 serial port.
See the section below titled "Serial port properties."
n
TerminalServer
. Select this if you want to connect the serial
interface on the controller to the server via a LAN. See the section
below titled "Terminal Server port properties."
n
LANVendor
. Select this if you want to connect the controller over a
TCP network. You can set the protocol choice in the ABB
TotalFlow channel properties or controller properties.
ATTENTION: Set the port properties to the same values as those
you specified when you configured the controller.
Serial port properties
Property
Description
Serial Port
Name
The device name of the serial port.
Baud rate
The number of data bits per second.
The default is
9600
.
Number of
Data Bits
The number of data bits used for transmission.
The default is
8
.
Stop Bits
The number of stop bits used for transmission
12
Chapter 2 - ABB Totalflow channel and controller reference


13
Property
Description
The default is
1
.
Parity
Defines parity verification of each character and must match
configuration on the end device.
The default is
NONE
.
Checksum
Specifies any checksum being added to the frame in addition to the
DB2 protocol error checks.
Not applicable, leave as
NONE
.
XON/XOFF
The type of XON/XOFF software flow control used to stop a receiver
from being overrun with messages from a sender. The types are:
l
Input
(use XON/XOFF to control the flow of data on the receive
line)
l
None
(default)
l
Output
(use XON/XOFF to control the flow of data on the transmit
line)
RS-232
Applicable only if the controller is connected to the RS-232 COM port.
Enable RTS/CTS flow control
. Select this if you want to use RTS/CTS for
flow control to stop a receiver from being overrun with messages from
a sender.
Detect DCD
. Select this if the Data Carrier Detect communication status
line of the COM port requires monitoring (usually when using modem
or microwave linking). When selected, the communications fails if the
desired COM status line is not high—for example, on a dial-up link
connection for a modem.
Detect DSR
. Select this if the Data Set Ready communication status line
of the COM port requires monitoring (usually when using modem or
microwave linking). When selected, the communications fails if the
desired COM status is not achieved.
RS-485
Applicable only if the controller is connected to the RS-485 COM port.
Enable Stallion RS-485 Half Duplex
. Select if RS-232 to RS-485 uses a
Stallion EasyConnection adapter.
Echo (Required for Stallion RS-485 ports)
. Select so that the server expects
the messages it sends to the port on the transmit line to be echoed
Chapter 2 - ABB Totalflow channel and controller reference