Authorization to discharge under the national pollutant discharge elimination system discharge requirements for publicly owned


Download 245.82 Kb.

bet1/2
Sana02.04.2018
Hajmi245.82 Kb.
  1   2

3800-PM-BPNPSM0012    Rev. 10/2013 

COMMONWEALTH OF PENNSYLVANIA 

 

Permit 

DEPARTMENT OF ENVIRONMENTAL PROTECTION 

 

BUREAU OF POINT AND NON-POINT SOURCE MANAGEMENT 

 



 

AUTHORIZATION TO DISCHARGE UNDER THE 

NATIONAL POLLUTANT DISCHARGE ELIMINATION SYSTEM 

DISCHARGE REQUIREMENTS FOR PUBLICLY OWNED 

TREATMENT WORKS (POTWs) 

3800-PM-WSFR0012    Rev. 8/2009 

NPDES PERMIT NO: PA0023451 

 

In  compliance  with  the  provisions  of  the  Clean  Water  Act,  33  U.S.C.  Section  1251  et  seq.  ("the  Act")  and 



Pennsylvania's Clean Streams Law, as amended, 35 P.S. Section 691.1 et seq.

 

Mount Jewett Borough Regional Sewer Authority McKean County 



PO Box 680  

Mount Jewett, PA  16740 

 

is  authorized  to  discharge  from  a  facility  known  as  the  Mount  Jewett  WWTP,  located  on  Kinzua  Street,  Mount 



Jewett, PA  16740, in Mount Jewett Borough, McKean County, to an Unnamed Tributary to the Kinzua Creek 

in Watershed 16-B in accordance with effluent limitations, monitoring requirements and other conditions set forth in 

Parts A, B and C hereof. 

 

THIS PERMIT SHALL BECOME EFFECTIVE ON 



__MAY 1, 2014____________ 

THIS PERMIT SHALL EXPIRE AT MIDNIGHT ON 

__APRIL 30, 2019___________ 

 

The authority granted by this permit is subject to the following further qualifications: 

 

1.  If  there  is  a  conflict  between  the  application,  its  supporting  documents  and/or  amendments  and  the  terms  and 



conditions of this permit, the terms and conditions shall apply. 

 

2.  Failure to comply with the terms, conditions or effluent limitations of this permit is grounds for enforcement action; 



for  permit  termination,  revocation  and  reissuance, or  modification;  or  for  denial  of  a  permit  renewal  application. 

(40 CFR 122.41(a)) 

 

3.  A complete application for renewal of this permit, or notice of intent to cease discharging by the expiration date, 



must  be  submitted  to  DEP  at  least  180  days  prior  to  the  above  expiration  date  (unless  permission  has  been 

granted by DEP for submission at a later date), using the appropriate NPDES permit application form. (40 CFR 

122.41(b), 122.21(d)) 

 

In the event that a timely and complete application for renewal has been submitted and DEP is unable, through 



no fault of the permittee, to reissue the permit before the above expiration date, the  terms and conditions of this 

permit,  including  submission  of  the  Discharge  Monitoring  Reports  (DMRs),  will  be  automatically  continued  and 

will  remain  fully  effective  and  enforceable  against  the  discharger  until  DEP  takes  final  action  on  the  pending 

permit application. (25 Pa. Code 92a.7(b), (c)) 

 

4.  This NPDES permit does not constitute authorization to construct or make modifications to wastewater treatment 



facilities necessary to meet the terms and conditions of this permit. 

 

DATE PERMIT ISSUED 

April 2, 2014 

 

ISSUED BY 

/s/ 

  

John A. Holden, P.E. 

 

Clean Water Program Manager 

Northwest Regional Office 

 

 



 

3800-PM-BPNPSM0012    Rev. 10/2013 

Permit 

 

 

Permit No. PA0023451 

 



PART A - EFFLUENT LIMITATIONS, MONITORING, RECORDKEEPING AND REPORTING REQUIREMENTS 

 

I. A.  For Outfall 

001 

,  Latitude 

41



 43

 53.00



 

,  Longitude 

78



 39



 01.00


 

,  River Mile Index 

N/A 

,  Stream Code 

N/A 




 

Receiving Waters: 

Unnamed Tributary to the Kinzua Creek 



 

Type of Effluent: 

treated municipal wastewater 

 

1.  The permittee is authorized to discharge during the period from Permit Effective Date through Permit Expiration Date. 



 

2.  Based on the anticipated wastewater characteristics and flows described in the permit application and its supporting documents and/or amendments, the 

following effluent limitations and monitoring requirements apply (see also Additional Requirements and Footnotes). 

 

Parameter 



Effluent Limitations 

Monitoring Requirements 

Mass Units (lbs/day) 

(1)

 

Concentrations (mg/L) 

Minimum 

(2)

 

Measurement 

Frequency 

Required 

Sample 

Type 

Average 

Monthly 

Weekly 

Average 

Minimum 

Average 

Monthly 

Weekly 

Average 

Instant. 

Maximum 

Flow (MGD) 

Report 

Report 


Daily Max 

XXX 


XXX 

XXX 


XXX 

Continuous 

Measured 

pH (S.U.) 

XXX 

XXX 


6.0 

XXX 


XXX 

9.0 


5/week 

Grab 


Dissolved Oxygen 

XXX 


XXX 

6.0 


XXX 

XXX 


XXX 

5/week 


Grab 

Total Residual Chlorine 

XXX 

XXX 


XXX 

0.5 


XXX 

1.6 


5/week 

Grab 


CBOD5 

104 


167 

XXX 


25 

40 


50 

1/week 


24-Hr 

Composite 

BOD5 

Influent 



XXX 

XXX 


XXX 

Report 


XXX 

XXX 


1/week 

24-Hr 


Composite 

Total Suspended Solids 

Influent 

XXX 


XXX 

XXX 


Report 

XXX 


XXX 

1/week 


24-Hr 

Composite 

Total Suspended Solids 

125 


188 

XXX 


30 

45 


60 

1/week 


24-Hr 

Composite 

Fecal Coliform (CFU/100 ml) 

May 1 - Sep 30 

XXX 

XXX 


XXX 

200 


Geo Mean 

XXX 


1,000 

1/week 


Grab 

Fecal Coliform (CFU/100 ml) 

Oct 1 - Apr 30 

XXX 


XXX 

XXX 


2,000 

Geo Mean 

XXX 

10,000 


1/week 

Grab 


Ammonia-Nitrogen 

May 1 - Oct 31 

6.3 

XXX 


XXX 

1.5 


XXX 

3.0 


1/week 

24-Hr 


Composite 

Ammonia-Nitrogen 

Nov 1 - Apr 30 

18.8 


XXX 

XXX 


4.5 

XXX 


9.0 

1/week 


24-Hr 

Composite 



3800-PM-BPNPSM0012    Rev. 10/2013 

Permit 

 

 

Permit No. PA0023451 

 



Outfall 001, Continued (from Permit Effective Date through Permit Expiration Date) 

 

Parameter 

Effluent Limitations 

Monitoring Requirements 

Mass Units (lbs/day) 

(1)

 

Concentrations (mg/L) 

Minimum 

(2)

 

Measurement 

Frequency 

Required 

Sample 

Type 

Average 

Monthly 

Weekly 

Average 

Minimum 

Average 

Monthly 

Weekly 

Average 

Instant. 

Maximum 

Total Nitrogen 

XXX 

XXX 


XXX 

Report 


XXX 

XXX 


1/week 

24-Hr 


Composite 

Total Phosphorus 

XXX 

XXX 


XXX 

Report 


XXX 

XXX 


1/week 

24-Hr 


Composite 

 

Samples taken in compliance with the monitoring requirements specified above shall be taken at the following location(s): 



 

at Outfall 001, after disinfection. 

  


3800-PM-BPNPSM0012    Rev. 10/2013 

Permit 

         

Permit No. PA0023451 

 



PART A - EFFLUENT LIMITATIONS, MONITORING, RECORDKEEPING AND REPORTING REQUIREMENTS 

(Continued) 

 

Additional Requirements 



 

1.  The permittee may not discharge: 

   

a.  Floating  solids,  scum,  sheen  or  substances  that  result  in  observed  deposits  in  the  receiving  water.  (25  Pa 



Code 92a.41(c)) 

 

b.  Oil  and  grease  in  amounts  that  cause  a  film  or  sheen  upon  or  discoloration  of  the  waters  of  this 



Commonwealth or adjoining shoreline, or that exceed 15 mg/l as a daily average or 30 mg/l at any time (or 

lesser amounts if specified in this permit).  (25 Pa. Code 92a.47(a)(7) and 95.2(2)) 

 

c.  Substances in concentration or amounts sufficient to be inimical or harmful to the water uses to be protected 



or to human, animal, plant or aquatic life.  (25 Pa Code 93.6(a)) 

 

d.  Foam  or substances  that  produce  an  observed  change  in  the  color,  taste,  odor  or  turbidity  of  the  receiving 



water,  unless those conditions are  otherwise controlled through  effluent limitations or other requirements in 

this permit.  (25 Pa Code 92a.41(c)) 

 

2.  The monthly average percent removal of BOD



5

 or CBOD


5

 and TSS must be at least 85% for POTW facilities on a 

concentration basis except where 25 Pa. Code 92a.47(g) and (h) are applicable to facilities with combined sewer 

overflows (CSOs) or as otherwise specified in this permit. (25 Pa. Code 92a.47(a)(3)) 

 

3.  If  the  permit  requires  the  reporting  of  average  weekly  statistical  results,  the  maximum  weekly  average 



concentration  and  maximum  weekly  average  mass  loading  shall  be  reported,  regardless  of  whether  the  results 

are obtained for the same or different weeks. 

 

4.  The permittee shall monitor the sewage effluent discharge(s) for the effluent parameters identified in the Part A 



limitations  table(s)  during  all  bypass  events  at  the  facility,  using  the  sample  types  that  are  specified  in  the 

limitations  table(s).    Where  the  required  sample  type  is  “composite”,  the  permittee  must  commence  sample 

collection  within  one  hour  of  the  start  of  the  bypass,  wherever  possible.    The  results  shall  be  reported  on  the 

Daily Effluent Monitoring supplemental form (3800-FM-BPNPSM0435) and be incorporated into the calculations 

used to report self-monitoring data on Discharge Monitoring Reports (DMRs). 

 

Footnotes 



 

(1)  When sampling to determine compliance with mass effluent limitations, the discharge flow at the time of sampling 

must be measured and recorded. 

 

(2)  This  is  the  minimum  number  of  sampling  events  required.    Permittees  are  encouraged,  and  it  may  be 



advantageous in demonstrating compliance, to perform more than the minimum number of sampling events. 

 

Supplemental Information 



 

(1)  The hydraulic design capacity of 0.5 million gallons per day for the treatment facility is used to prepare the annual 

Municipal Wasteload  Management  Report  to help  determine  whether  a  "hydraulic  overload"  situation  exists,  as 

defined in Title 25 Pa. Code Chapter 94. 

 

(2)  The effluent limitations for Outfall 001 were determined using an effluent discharge rate of 0.5 MGD. 



 

(3)  The  organic  design  capacity  of  834  lbs  BOD

5

  per  day  for  the  treatment  facility  is  used  to  prepare  the  annual 



Municipal  Wasteload  Management  Report  to  determine  whether  an  “organic  overload”  condition  exists,  as 

defined in 25 Pa. Code Chapter 94. 

 

(4)  Total  Nitrogen  is  the  sum  of  Total  Kjeldahl-N  (TKN)  plus  Nitrite-Nitrate  as  N  (NO



2

+NO


3

-N),  where  TKN  and 

NO

2

+NO



3

-N are measured in the same sample. 



3800-PM-BPNPSM0012    Rev. 10/2013 

Permit 

         

Permit No. PA0023451 

 



II. 

DEFINITIONS 

 

At Outfall (XXX) means a sampling location in outfall line XXX below the last point at which wastes are added 

to outfall line (XXX), or where otherwise specified. 

 

Average  refers  to  the  use  of  an  arithmetic  mean,  unless  otherwise  specified  in  this  permit.  (40  CFR 

122.41(l)(4)(iii)) 

 

Best  Management  Practices  (BMPs)  means  schedules  of  activities,  prohibitions  of  practices,  maintenance 

procedures  and  other  management  practices  to  prevent  or  reduce  the  pollution  to  surface  waters  of  the 

Commonwealth.    BMPs  also  include  treatment  requirements,  operating  procedures  and  practices  to  control 

plant  site  runoff,  spillage  or  leaks,  sludge  or  waste  disposal,  or  drainage  from  raw  material  storage.  (25  Pa. 

Code 92a.2) 



 

Bypass  means  the  intentional  diversion  of  waste  streams  from  any  portion  of  a  treatment  facility.  (40  CFR 

122.41(m)(1)(i)) 

 

Calendar Week is defined as the seven consecutive days from Sunday through Saturday, unless the permittee 

has  been  given  permission  by  DEP  to  provide  weekly  data  as  Monday  through  Friday  based  on  showing 

excellent performance of the facility and a history of compliance. In cases when the week falls in two separate 

months, the month with the most days in that week shall be the month for reporting. 

 

Clean Water Act means the Federal Water Pollution Control Act, as amended (33 U.S.C.A. §§1251 to 1387). 

 

Composite Sample (for all except GC/MS volatile organic analysis) means a combination of individual samples 

(at least eight for a 24-hour period or four for an 8-hour period) of at least 100 milliliters (mL) each obtained at 

spaced  time  intervals  during  the  compositing  period.    The  composite  must  be  flow-proportional;  either  the 

volume of each individual sample is proportional to discharge flow rates, or the sampling interval is proportional 

to the flow rates over the time period used to produce the composite. (EPA Form 2C) 

 

Composite  Sample  (for  GC/MS  volatile  organic  analysis)  consists  of  at  least  four  aliquots  or  grab  samples 

collected during the sampling event (not necessarily flow proportioned).  The samples must be combined in the 

laboratory immediately before analysis and then one analysis is performed. (EPA Form 2C) 

 

Daily  Average  Temperature  means  the  average  of  all  temperature  measurements  made,  or  the  mean  value 

plot of the record of a continuous automated temperature recording instrument, either during a calendar day or 

during the operating day if flows are of a shorter duration. 

 

Daily Discharge means the discharge of a pollutant measured during a calendar day or any 24-hour period that 

reasonably represents the calendar day for purposes of sampling.  For pollutants with limitations expressed in 

units  of  mass,  the  "daily  discharge"  is  calculated  as  the  total  mass  of  the  pollutant  discharged  over  the  day.  

For pollutants with limitations expressed in other units of measurement, the "daily discharge" is calculated as 

the average measurement of the pollutant over the day. (25 Pa. Code 92a.2, 40 CFR 122.2) 

 

Daily Maximum Discharge Limitation means the highest allowable "daily discharge." 

 

Discharge  Monitoring  Report  (DMR)  means  the  DEP  or  EPA  supplied  form(s)  for  the  reporting  of  self-

monitoring results by the permittee. (25 Pa. Code 92a.2 and 40 CFR 122.2) 

 

Estimated  Flow  means  any  method  of  liquid  volume  measurement  based  on  a  technical  evaluation  of  the 

sources  contributing  to the  discharge  including,  but  not limited  to,  pump  capabilities,  water  meters  and  batch 

discharge volumes. 

 

Geometric Mean means the average of a set of n sample results given by the n

th

 root of their product. 



 

Grab  Sample  means  an  individual  sample  of  at  least  100  mL  collected  at  a  randomly  selected  time  over  a 

period not to exceed 15 minutes. (EPA Form 2C) 



3800-PM-BPNPSM0012    Rev. 10/2013 

Permit 

         

Permit No. PA0023451 

 



Hauled-In Wastes means any waste that is introduced into a treatment facility through any method other than a 

direct connection to the sewage collection system.  The term includes wastes transported to and disposed of 

within the treatment facility or other entry points within the collection system. 

 

Hazardous  Substance  means  any  substance  designated  under  40  CFR  Part  116  pursuant to  Section  311  of 

the Clean Water Act. (40 CFR 122.2) 

 

Immersion  Stabilization  (i-s)  means  a  calibrated  device  is  immersed  in  the  wastewater  until  the  reading  is 

stabilized. 



 

Indirect  Discharger  means  a  non-domestic  discharger  introducing  pollutants  to  a  Publicly  Owned  Treatment 

Works (POTW) or other treatment works.  (25 Pa. Code 92a.2 and 40 CFR 122.2) 



 

Industrial User means a source of Indirect Discharge. (40 CFR 403.3) 

 

Instantaneous Maximum Effluent Limitation means the highest allowable discharge of a concentration or mass 

of a substance at any one time as measured by a grab sample. (25 Pa. Code 92a.2) 

 

Measured Flow means any method of liquid volume measurement, the accuracy of which has been previously 

demonstrated in engineering practice, or for which a relationship to absolute volume has been obtained. 

 

Monthly  Average  Discharge  Limitation  means  the  highest  allowable  average  of  "daily  discharges"  over  a 

calendar month, calculated as the sum of all "daily discharges" measured during a calendar month divided by 

the number of "daily discharges" measured during that month. (25 Pa. Code 92a.2) 

 

Municipality means a city, town, borough, county, township, school district, institution, authority or other public 

body created by or pursuant to State law and having jurisdiction over disposal of sewage, industrial wastes, or 

other wastes. (25 Pa. Code 92a.2) 

 

Publicly  Owned  Treatment Works  (POTW) means  a  treatment  works  as  defined  by  §212  of  the  Clean Water 

Act,  owned  by  a  state  or  municipality.    The  term  includes  any  devices  and  systems  used  in  the  storage, 

treatment, recycling and reclamation of municipal sewage or industrial wastes of a liquid nature. The term also 

includes sewers, pipes or other conveyances if they  convey wastewater to a POTW providing treatment. The 

term  also means  the  municipality  as  defined  in  section  502(4)  of  the  Clean Water  Act,  which  has  jurisdiction 

over  the  indirect  discharges  to  and  the  discharges  from  such  a  treatment  works.  (25  Pa  Code  92a.2  and  40 

CFR 122.2) 

 

Severe  Property  Damage  means  substantial  physical  damage  to  property,  damage  to  the  treatment  facilities 

that  causes  them  to  become  inoperable,  or  substantial  and  permanent  loss  of  natural  resources  that  can 

reasonably  be  expected  to  occur  in  the  absence  of  a  bypass.    Severe  property  damage  does  not  mean 

economic loss caused by delays in production. (40 CFR 122.41(m)(1)(ii)) 

 

Stormwater  means  the  runoff  from  precipitation,  snow  melt  runoff,  and  surface  runoff  and  drainage.  (25  Pa. 

Code 92a.2) 

 

Stormwater  Associated  With  Industrial  Activity  means  the  discharge  from  any  conveyance  that  is  used  for 

collecting and conveying stormwater and that is directly related to manufacturing, processing or raw  materials 

storage areas at an industrial plant, and as defined at 40 CFR §122.26(b)(14)(i) 

 (ix) and (xi) and 25 Pa. Code 



92a.2. 

 

Toxic Pollutant means those pollutants, or combinations of pollutants, including disease-causing agents, which 

after discharge and upon exposure, ingestion, inhalation or assimilation into any organism, either directly from 

the  environment  or  indirectly  by  ingestion  through  food  chains  may,  on  the  basis  of  information  available  to 

DEP  cause  death,  disease,  behavioral  abnormalities,  cancer,  genetic  mutations,  physiological  malfunctions, 

including malfunctions in reproduction, or physical deformations in these organisms or their offspring.  (25 Pa. 

Code 92a.2) 

 

Weekly  Average  Discharge  Limitation  means  the  highest  allowable  average  of  "daily  discharges"  over  a 

calendar week, calculated as the sum of all "daily discharges" measured during a calendar week divided by the 

number of "daily discharges" measured during that week. 



3800-PM-BPNPSM0012    Rev. 10/2013 

Permit 

         

Permit No. PA0023451 

 



III. 

SELF-MONITORING, REPORTING AND RECORDKEEPING 

 

A.  Representative Sampling 



 

1.  Samples  and  measurements  taken  for  the  purpose  of  monitoring  shall  be  representative  of  the 

monitored activity (40 CFR 122.41(j)(1)).  Representative sampling includes the collection of samples, 

where  possible,  during  periods  of  adverse  weather,  changes  in  treatment  plant  performance  and 

changes in treatment plant loading.  If possible, effluent samples must be collected where the effluent 

is  well  mixed  near  the  center  of  the  discharge  conveyance  and  at  the  approximate  mid-depth  point, 

where the turbulence is at a maximum and the settlement of solids is minimized. (40 CFR 122.48 and 

25 Pa. Code § 92a.61) 

 

2.  Records Retention (40 CFR 122.41(j)(2)) 



 

Except  for  records  of  monitoring  information  required  by  this  permit  related  to  the  permittee's  sludge 

use  and  disposal  activities  which  shall  be  retained  for  a  period  of  at  least  5  years,  all  records  of 

monitoring  activities  and  results  (including  all  original  strip  chart  recordings  for  continuous  monitoring 

instrumentation and calibration and maintenance records), copies of all reports required by this permit, 

and  records  of  all  data  used  to  complete  the  application  for  this  permit  shall  be  retained  by  the 

permittee for 3 years from the date of the sample measurement, report or application

unless a longer 



retention period is required by the permit.  The 3-year period shall be extended as requested by DEP 

or the EPA Regional Administrator.  

 

3.  Recording of Results (40 CFR 122.41(j)(3)) 



 

For  each  measurement  or  sample  taken  pursuant  to  the  requirements  of  this  permit,  the  permittee 

shall record the following information: 

 

a.  The exact place, date and time of sampling or measurements. 



b.  The person(s) who performed the sampling or measurements. 

c.  The date(s) the analyses were performed. 

d.  The person(s) who performed the analyses. 

e.  The analytical techniques or methods used; and the associated detection level. 

f. 

The results of such analyses. 



 

4.  Test Procedures (40 CFR 122.41(j)(4)) 

 

Facilities that test or analyze environmental samples used to demonstrate compliance with this permit 



shall  be  in  compliance  with  laboratory  accreditation  requirements  of  Act  90  of  2002  (27  Pa.  C.S. 

§§4101-4113)  and  25  Pa.  Code  Chapter  252,  relating  to  environmental  laboratory  accreditation.  

Unless  otherwise  specified  in  this  permit,  the  test  procedures  for  the  analysis  of  pollutants  shall  be 

those approved under 40 CFR Part 136 (or in the case of sludge use or disposal, approved under 40 

CFR  Part  136,  unless  otherwise  specified  in  40  CFR  Part  503  or  Subpart  J  of  25  Pa.  Code  Chapter 

271), or alternate test procedures approved pursuant to those parts, unless other test procedures have 

been specified in this permit. 

 

5.  Quality/Assurance/Control 



 

In an effort to assure accurate self-monitoring analyses results: 

 

a.  The  permittee,  or  its  designated  laboratory,  shall  participate  in  the  periodic  scheduled  quality 



assurance inspections conducted by DEP and EPA. (40 CFR 122.41(e), 122.41(i)(3)) 

 

b.  The permittee, or its designated laboratory, shall develop and implement a program to assure the 



quality  and  accurateness  of  the  analyses  performed  to  satisfy  the  requirements  of  this  permit,  in 

accordance with 40 CFR Part 136. (40 CFR 122.41(j)(4)) 

 


3800-PM-BPNPSM0012    Rev. 10/2013 

Permit 

         

Permit No. PA0023451 

 



B.  Reporting of Monitoring Results 

 

1.  The  permittee  shall  effectively  monitor  the  operation  and  efficiency  of  all  wastewater  treatment  and 



control  facilities,  and  the  quantity  and  quality  of  the  discharge(s)  as  specified  in  this  permit.  (40  CFR 

122.41(e), 122.44(i)(1)) 

 

2.  Discharge  Monitoring  Reports  (DMRs) must  be  completed  in  accordance 



with DEP’s published DMR 

Instructions (3800-FM-BPNPSM0463).  DMRs are based on calendar reporting periods.  DMR(s) must 

be  received  by  the  agency(ies)  specified  in  paragraph  3  below  in  accordance  with  the  following 

schedule: 

 

 -    Monthly DMRs must be received within 28 days following the end of each calendar month. 



 

-     Quarterly DMRs must be received within 28 days following the end of each calendar quarter, i.e., 

January 28, April 28, July 28, and October 28. 

 



Semiannual DMRs must be received within 28 days following the end of each calendar semiannual 

period, i.e., January 28 and July 28. 

 



Annual DMRs must be received by January 28, unless Part C of this permit requires otherwise.   



 

3.  The  permittee  shall  complete  all  Supplemental  Reporting  forms  (Supplemental  DMRs)  provided  by 

DEP  in  this  permit  (or  an  approved  equivalent),  and  submit  the  signed,  completed  forms  as  an 

attachment  to the  DMR(s).  If  the  permittee  elects  to use 

DEP’s

  electronic  DMR  (eDMR)  system,  one 



electronic submission may be made for DMRs and Supplemental DMRs.  If paper forms are used, the 

completed forms shall be mailed to: 

Department of Environmental Protection 



Clean Water Program 

230 Chestnut Street 

Meadville, PA  16335-3481 

 

4.  If the permittee elects to begin using DEP's eDMR system to submit DMRs required by the permit, the 



permittee shall, to assure continuity of business operations, continue using the eDMR system to submit 

all DMRs and Supplemental Reports required by the permit, unless the following steps are completed 

to discontinue use of eDMR: 

 

a.  The  permittee  shall  submit  written  notification  to  the  regional  office  that  issued  the  permit  that  it 



intends to discontinue use of eDMR. The notification shall be signed by a principal executive officer 

or authorized agent of the permittee. 

 

b.  The  permittee  shall  continue  using  eDMR  until  the  permittee  receives  written  notification  from 



DEP's  Central  Office  that  the  facility  has  been  removed  from  the  eDMR  system,  and  electronic 

report submissions are no longer expected. 

 

5.  The completed DMR Form shall be signed and certified by either of the following applicable persons, 



as defined in 25 Pa. Code § 92a.22: 

 



For  a  corporation  -  by  a  principal  executive  officer  of  at  least  the  level  of  vice  president,  or  an 

authorized representative, if the representative is responsible for the overall operation of the facility 

from which the discharge described in the NPDES form originates. 

For a partnership or sole proprietorship - by a general partner or the proprietor, respectively. 



For a municipality, state, federal or other public agency - by a principal executive officer or ranking 

elected official. 

 

If signed by a person other than the above, written notification of delegation of DMR signatory authority 



must be submitted to DEP in advance of or along with the relevant DMR form.  (40 CFR 122.22(b)) 

 


3800-PM-BPNPSM0012    Rev. 10/2013 

Permit 

         

Permit No. PA0023451 

 



6.  If  the  permittee  monitors  any  pollutant  at  monitoring  points  as  designated  by  this  permit,  using 

analytical  methods  described  in  Part  A  III.A.4.  herein,  more  frequently  than  the  permit  requires,  the 

results of this monitoring shall be incorporated, as appropriate, into the calculations used to report self-

monitoring data on the DMR.  (40 CFR  122.41(l)(4)(ii))  

 

C.  Reporting and Notification Requirements 



 

1.  Planned Changes to Physical Facilities 

 The permittee shall give notice to DEP as soon as possible 



but no later than 30 days prior to  planned physical alterations or additions to the permitted facility.  A 

permit under 25 Pa. Code  Chapter 91 may be required for these situations  prior  to implementing the 

planned changes.  A permit application, or other written submission to DEP, can be used to satisfy the 

notification requirements of this section.   

 

 

Notice is required when: 



 

a.  The  alteration  or  addition  to  a  permitted  facility  may  meet  one  of  the  criteria  for  determining 

whether a facility is a new source in 40 CFR §122.29(b). (40 CFR 122.41(l)(1)(i)) 

 

b.  The  alteration  or  addition  could  significantly  change  the  nature  or  increase  the  quantity  of 



pollutants  discharged.    This  notification  applies  to  pollutants  which  are  not  subject  to  effluent 

limitations in this permit. (40 CFR 122.41(l)(1)(ii)) 

 

c.  The alteration or addition results in a significant change in the permittee's sludge use or disposal 



practices, and such alteration, addition, or change may justify the application of permit conditions 

that  are  different  from  or  absent  in  the  existing  permit,  including  notification  of  additional  use  or 

disposal  sites  not  reported  during  the  permit  application  process  or  not  reported  pursuant  to  an 

approved land application plan. (40 CFR 122.41(l)(1)(iii)) 

 

d.  The planned change may result in noncompliance with permit requirements.  (40 CFR 122.41(l)(2)) 



 

2.  Planned  Changes  to  Waste  Stream 

  Under  the  authority  of  25  Pa.  Code  92a.24(a)  and  40  CFR 



122.42(b), the permittee shall provide notice to DEP and EPA as soon as possible but no later than 45 

days prior to any planned changes in the volume or pollutant concentration of its influent waste stream 

as a result of indirect discharges or hauled-in wastes, as specified in paragraphs 2.a. and 2.b., below.  

Notice shall be provided on the “Planned Changes to Waste Stream” Supplemental Report (3800

-FM-

BPNPSM0482),  available  on  DEP’s  website.    The  permittee  shall  provide  information  on  the  quality 



and  quantity  of  waste  introduced  into  the  POTW,  and  any  anticipated  impact  of  the  change  on  the 

quantity  or  quality  of  effluent  to  be  discharged  from  the  POTW  (40  CFR  122.42(b)(3)).    The  Report 

shall be sent via Certified Mail or other means to confirm DEP’s rece

ipt  of  the  notification.    DEP  will 

determine if the submission of a new application and receipt of a new or amended permit is required.   

 

a.  Introduction of New Pollutants (25 Pa. Code 92a.24(a), 40 CFR 122.42(b)(1)) 



 

 

New pollutants are defined as parameters that meet one or more of the following criteria: 



 

(i) 


Were not detected in the facilities’ influent waste stream as reported in the permit application; 

and have not been approved to be included in the permittee’s influent waste stream by DEP in 

writing. 

 

(ii)  Are  previously  unapproved  pollutants  introduced  into  the  POTW  from  an  indirect  discharger 



which  would  be  subject  to  Sections  301  and  306  of  the  Clean  Water  Act  if  it  were  directly 

discharging those pollutants (40 CFR 122.42(b)(1)). 

 

 

The  permittee  shall  provide  notification  of  the  introduction  of  new  pollutants  in  accordance  with 



paragraph  2  above.   The  permittee may  not  authorize  the  introduction  of  new  pollutants  until  the 

permittee receives DEP’s written approval.

 

 

b.  Increased Loading of Approved Pollutants (25 Pa. Code 92a.24(a), 40 CFR 122.42(b)(2)) 



3800-PM-BPNPSM0012    Rev. 10/2013 

Permit 

         

Permit No. PA0023451 

 

10 



 

 

Approved pollutants are defined as parameters that meet one or more of the following criteria: 



 

(i) 


Were  detected  in  the  facilities’  influent  waste  stream  as  reported  in  the  permittee’s  permit 

application; or 

have been previously approved to be included in the permittee’s influent waste 

stream by DEP in writing. 

 

(ii)  Have an effluent limitation or monitoring requirement in this permit. 



 

 

The permittee shall provide notification of the introduction of increased influent loading (lbs/day) of 



approved  pollutants  in  accordance  with  paragraph  2  above  when  (1)  the  cumulative  increase  in 

influent loading (lbs/day) exceeds 20% of the maximum loading reported in the permit application, 

or  a  loading  previously  approved  by  DEP  and/or  EPA,  or  (2)  may  cause  an  exceedance  in  the 

effluent of  Effluent Limitation  Guidelines  (ELGs)  or  limitations  in  Part  A  of  this  permit,  or  (3) may 

cause interference or pass through at the POTW, or (4) may cause exceedances of the applicable 

water quality standards in the receiving stream.  Unless specified otherwise in this permit, if DEP 

does not respond to the notification  within 30  days of its receipt, the  permittee  may proceed  with 

the  increase  in  loading.    The  acceptance  of  increased  loading  of  approved  pollutants  may  not 

result  in  an  exceedance  of  ELGs  or  effluent  limitations,  may  not  result  in  a  hydraulic  or  organic 

overload  condition  as  defined  in  25  Pa.  Code  94.1,  and  may  not  cause  exceedances  of  the 

applicable water quality standards in the receiving stream.  

 

3.  Reporting Requirements for Hauled-In Wastes 



 

a.  Receipt of Residual Waste 

 

(i)  The  permittee  shall  document  the  receipt  of  all  hauled-in  residual  wastes  (including  but  not 



limited to wastewater from oil and gas wells, food processing waste, and landfill leachate), as 

defined at 25 Pa. Code § 287.1, that are received for processing at the treatment facility.  The 

permittee shall report hauled-

in residual wastes on a monthly basis to DEP on the “Hauled In 

Residual  Wastes”  Supplemental  Repo

rt  (3800-FM-BPNPSM0450)  as  an  attachment  to  the 

DMR.    If  no  residual  wastes  were  received  during  a  month,  submission  of  the  Supplemental 

Report is not required.   

 

The  following  information  is  required  by  the  Supplemental  Report.    The  information  used  to 



develop  the  Report  shall  be  retained  by  the  permittee  for  five  years  from  the  date  of  receipt 

and must be made available to DEP or EPA upon request. 

 

(1)  The dates that residual wastes were received. 



 

(2)  The volume (gallons) of wastes received. 

 

(3)  The license plate number of the vehicle transporting the waste to the treatment facility. 



 

(4)  The permit number(s) of the well(s) where residual wastes were generated, if applicable. 

 

(5)  The name and address of the generator of the residual wastes. 



 

(6)  The type of wastewater. 

 

The  transporter  of  residual  waste  must maintain  these  and  other  records  as  part  of  the  daily 



operational  record  (25  Pa.  Code  §  299.219).    If  the  transporter  is  unable  to  provide  this 

information or the permittee has not otherwise received the information from the generator, the 

residual  wastes  shall  not  be  accepted  by  the  permittee  until  such  time  as  the  permittee 

receives such information from the transporter or generator. 

 

(ii)  The  following  conditions  apply  to  the  characterization  of  residual  wastes  received  by  the 



permittee: 

3800-PM-BPNPSM0012    Rev. 10/2013 

Permit 

         

Permit No. PA0023451 

 

11 



 

(1)  If  the  generator  is  required  to  complete  a  chemical  analysis  of  residual  wastes  in 

accordance with 25 Pa. Code § 287.51, the permittee must receive and maintain on file a 

chemical analysis of the residual wastes it receives.  The chemical analysis must conform 

to the Bureau of Waste Management’s Form 26R except as noted in paragraph (2), below.  

Each  load  of  residual  waste  received  must  be  covered  by  a  chemical  analysis  if  the 

generator is required to complete it. 

 

(2)  For  wastewater  generated  fro



m  hydraulic  fracturing  operations  (“frac  wastewater”)  within 

the  first  30  production  days  of  a  well  site,  the  chemical  analysis  may  be  a  general  frac 

wastewater characterization approved by DEP.  Thereafter, the chemical analysis must be 

waste-specific and be reported on the Form 26R. 

 

b.  Receipt of Municipal Waste 



 

(i)  The  permittee  shall  document  the  receipt of  all  hauled-in  municipal  wastes  (including  but not 

limited  to  septage  and  liquid  sewage  sludge),  as  defined  at  25  Pa.  Code  §  271.1,  that  are 

received for processing at the treatment facility.  The permittee shall report hauled-in municipal 

wastes on a monthly basis to DEP on the “Hauled In Municipal Wastes” Supplemental Report 

(3800-FM-BPNPSM0437)  as  an  attachment  to  the  DMR.    If  no  municipal  wastes  were 

received during a month, submission of the Supplemental Report is not required.   

 

The following information is required by the Supplemental Report: 



 

(1)  The dates that municipal wastes were received. 

 

(2)  The volume (gallons) of wastes received. 



 

(3)  The BOD

5

 concentration (mg/l) and load (lbs) for the wastes received. 



 

(4)  The location(s) where wastes were disposed of within the treatment facility. 

 

(ii)  Sampling  and  analysis  of  hauled-in  municipal  wastes  must  be  completed  to  characterize  the 



organic strength of the wastes, unless composite sampling of influent wastewater is performed 

at  a  location  downstream  of  the  point  of  entry  for  the  wastes.    The  influent  BOD

5

 

characterization  for  the  treatment  facility,  as  reported  in  the  annual  Municipal  Wasteload 



Management  Report  per  25  Pa.  Code  Chapter  94,  must  be  representative  of  the  hauled-in 

municipal wastes received.  

  

 


3800-PM-BPNPSM0012    Rev. 10/2013 

Permit 

         

Permit No. PA0023451 

 

12 



4.  Unanticipated Noncompliance or Potential Pollution Reporting 

 

a.  Immediate Reporting - The permittee shall immediately report any incident causing  or threatening 



pollution in accordance with the requirements of 25 Pa. Code Sections 91.33 and 92a.41(b). 

 

(i)  If,  because  of  an  accident,  other  activity  or  incident  a  toxic  substance  or  another  substance 



which  would  endanger  users  downstream  from  the  discharge,  or  would  otherwise  result  in 

pollution  or  create  a  danger  of  pollution  or  would  damage  property,  the  permittee  shall 

immediately notify DEP by telephone of the location and nature of the danger.  Oral notification 

to the Department is required as soon as possible, but no later than 4 hours after the permittee 

becomes aware of the incident causing or threatening pollution. 

 

(ii)  If reasonably possible to do so, the permittee shall immediately notify downstream users of the 



waters  of  the  Commonwealth  to  which  the  substance  was  discharged.  Such  notice  shall 

include the location and nature of the danger.   

 

(iii)  The permittee shall immediately take or cause to be taken steps necessary to prevent injury to 



property  and  downstream  users  of  the  waters  from  pollution  or  a  danger  of  pollution  and,  in 

addition,  within  15  days  from  the  incident,  shall  remove  the  residual  substances  contained 

thereon or therein from the ground and from the affected waters of this Commonwealth to the 

extent required by applicable law.  

 

b.  The  permittee  shall  report  any  noncompliance  which  may  endanger  health  or  the  environment  in 



accordance  with  the  requirements  of  40  CFR  122.41(l)(6).    These  requirements  include  the 

following obligations:   

 

(i)  24 Hour Reporting - The permittee shall orally report any noncompliance with this permit which 



may endanger health or the environment within 24 hours from the time the permittee becomes 

aware  of  the  circumstances.    The  following  shall  be  included  as  information  which  must  be 

reported within 24 hours under this paragraph (40 CFR 122.41(l)(6)(ii)): 

 

(1)  Any unanticipated bypass which exceeds any effluent limitation in the permit



 

(2)  Any upset which exceeds any effluent limitation in the permit; and 

 

(3)  Violation  of  the  maximum  daily  discharge  limitation  for  any  of  the  pollutants  listed  in  the 



permit as being subject to the 24-hour reporting requirement. 

 

(ii)  Written  Report  -  A  written  submission  shall  also  be  provided  within  5  days  of  the  time  the 



permittee  becomes  aware  of  any  noncompliance  which  may  endanger  health  or  the 

environment.  The written submission shall contain a description of the noncompliance and its 

cause;  the  period  of  noncompliance,  including  exact  dates  and  times,  and  if  the 

noncompliance  has  not  been  corrected,  the  anticipated  time  it  is  expected  to  continue;  and 

steps taken or planned to reduce, eliminate, and prevent reoccurrence of the noncompliance. 

 

(iii)  Waiver  of  Written  Report  -  DEP  may  waive  the  written  report  on  a  case-by-case  basis  if  the 



associated oral report has been received within 24 hours from the time the permittee becomes 

aware  of  the  circumstances  which  may  endanger  health  or  the  environment.    Unless  such  a 

waiver is expressly granted by DEP, the permittee shall submit a written report in accordance 

with this paragraph. (40 CFR 122.41(l)(6)(iii)) 

 

5.  Other Noncompliance 



 

The  permittee  shall  report  all  instances  of  noncompliance  not  reported  under  paragraph  C.4  of  this 

section  or  specific  requirements  of  compliance  schedules,  at  the  time  DMRs  are  submitted,  on  the 

Non-Compliance Reporting Form (3800-FM-BPNPSM0440). The reports shall contain the information 

listed in paragraph C.4.b.(ii) of this section. (40 CFR 122.41(l)(7)) 


3800-PM-BPNPSM0012    Rev. 10/2013 

Permit 

         

Permit No. PA0023451 

 

13 





Do'stlaringiz bilan baham:
  1   2


Ma'lumotlar bazasi mualliflik huquqi bilan himoyalangan ©fayllar.org 2017
ma'muriyatiga murojaat qiling