8.4.1 Signature analysis
Signatures are characteristic graphical representations of electromagnetic phenomena. For example, the
energization of a certain type of load may consistently generate the same waveshape disturbance. This wave-
shape would be called its
signature. Seeing this signature in a monitoring situation identiÞes
the presence of
that load.
Many, but by no means all, electromagnetic phenomena have signatures that can be recognized and ana-
lyzed. The more information provided by a graph, the greater the possibility that a disturbance can be identi-
Þed by its signature. Sag/swell graphs, for example, showing simultaneous
voltage and current, may more
quickly lead to correct conclusions than those showing a voltage sag or swell alone.
8.4.2 Steady-state waveshape analysis
8.4.2.1 Scope
There is much that can be learned from examining the normal, steady-state waveshape of loads or the power
system. This type of analysis does not focus on disturbances, but rather on
what might be happening when
Table 1ÑReference chart for problem analysis
Typical problems
Disturbance
type
Possible causes
Subclause
Overheated neutral
Intermittent lock-ups
Frequency deviations
Steady-state
Shared neutrals
Improper
or inadequate wiring
High source impedance
SCR/RectiÞers and notching
Harmonics
8.4.2
Interruption
Garbled data
Random increases in harmonic levels
Utility faults
Inrush currents
Inadequate wiring
8.4.3
Intermittent lockups
Lights ßicker
Garbled data
Sag/swell
Source voltage variations
Inrush/surge currents
Inadequate wiring
8.4.4
Component failure
Dielectric
breakdown
Lock-ups
Garbled data
Wavy CRTs
Impulses
EMI/RFI
Lightning
Load switching
Capacitor switching
Static discharge
Hand-held radios
Loose wiring/arcing
8.4.5
Overheated transformers
Voltage
distortion
Current distortion
Overheated motors
Garbled Data
Lock-ups
Harmonics
Electronic loads
SCR/rectiÞer
Loads bandwidth of source impedance
8.4.6
Problems occur at the same time
Problems
occur at regular intervals
All
Timed loads
Cyclical loads
8.4.7
SPS and/or automatic transfer switch
does not work
Excessive frequency shift
Discontinuities
Switching to alternate sources
Non-synchronized power switching
8.4.8
IEEE
MONITORING ELECTRIC POWER QUALITY
Std 1159-1995
53
there are no disturbances. Typically, waveshape analysis is more useful at the facility
level or further down-
stream as opposed to the utility level.
Steady-state waveshape analysis provides information regarding the following:
a)
Type of loads
b)
Adequacy of power system
c)
VeriÞcation of wiring practices (shared vs. dedicated neutral)