Power Plant Engineering
Synthetic Transformer Oil
Download 3.45 Mb. Pdf ko'rish
|
Power-Plant-Engineering
- Bu sahifa navigatsiya:
- 5. Temperature Rise.
- 12.5.1 SINGLE BUS-BAR SYSTEM
- Disadvantages
4. Synthetic Transformer Oil. This has been developed to avoid the risk of fire and explosion,
present always with normal mineral oils. Chlorinated diphenyl, a synthetic oil suitable for transformers, is chemically stable, non-oxidizing, rather volatile, and heavier than water. Its dielectric strength is higher than that of mineral oil, and moisture has a smaller tendency to migrate through it. The per- mittivity is 4.5, compared with about 2.5. This high figure is roughly the same as the permittivity of the solid insulating material used in a transformer, so that the distribution of electric stress will differ mark- edly from that when mineral oil is used, the stress in the oil being relieved at the expense of the solid insulation. The oil is a powerful solvent of most varnishes, gums, binders and paints, which must conse- quently be barred from transformers designed for synthetic oil cooling. When decomposed by electric are, hydrogen chloride gas is the chief product: this may combine with water to form hydrochloric acid. 5. Temperature Rise. The temperature rises permitted in the British Standard Specification for power and lighting transformers. ELECTRICAL SYSTEM 409 12.5 BUS-BAR When a number of generators or feeders operating at the same voltage have to be directly con- nected electrically, bus-bars are used as the common electrical component. Bus-bars are copper rods or thin walled tubes and operate at constant voltage. We shall discuss some important bus-bars arrange- ments used for power stations and sub-stations. All the diagrams refer to 3-phase arrangement but are shown in single-phase for simplicity. 12.5.1 SINGLE BUS-BAR SYSTEM The single bus-bar system has the simplest de- sign and is used for power stations. It is also used in small outdoor stations having relatively few outgoing or incom-ing feeders and lines. Fig. 12.28 shows the single bus-bar system for a typical power station. The generators, outgoing lines and transformers are connected to the bus-bar. Each generator and feeder is controlled by a circuit breaker. The isolators permit to isolate generators, feeders and circuit breakers from the bus-bar for maintenance. The chief advantages of this type of arrangement are low initial cost, less maintenance and simple operation. Disadvantages Single bus-bar system has the following three principal disadvantages (1) The bus-bar cannot be cleaned, repaired or tested without de-energizing the whole system. (2) If a fault occurs on the bus-bar itself, there is complete interruption of supply. (3) Any fault on the system is fed by all the generating capacity, resulting in very large fault currents. Download 3.45 Mb. Do'stlaringiz bilan baham: |
Ma'lumotlar bazasi mualliflik huquqi bilan himoyalangan ©fayllar.org 2024
ma'muriyatiga murojaat qiling
ma'muriyatiga murojaat qiling