Pursuant to Article 116 of the Energy Law
Download 0.65 Mb. Pdf ko'rish
|
Serbian Grid Code-1-43
- Bu sahifa navigatsiya:
- 4.2.7. QUALITY OF THE VOLTAGE WAVE
- 4.2.7.2. Higher harmonics 4.2.7.2.1.
POWER
ABSORPTION FROM TRANSMISSION GRID 4.2.6.1. Users of transmission grid should secure conditions during regular operation of their facilities in such a way that the reactive and active power ration absorbed from the transmission grid in the connection/inter-connection point is below 0.33 at each 15 min interval, with the measuring system registering interchange of reactive and active energy except for the points where generation units are connected in accordance with the Grid Code and section 4.3.7. 4.2.7. QUALITY OF THE VOLTAGE WAVE 4.2.7.1. Current asymmetry 4.2.7.1.1. The current asymmetry caused by the facility of transmission system user must not exceed: - 2% if the facility is connected/inter-connected to the 110 kV grid; - 1.4% if the facility is connected to the 220 kV grid. - 0.8% if the facility is connected to the 400 kVgrid. 4.2.7.1.2. Exceptionally, for facilities connected to the 110 kV grid supplying the railways (so called electro-traction substation) the JSC EMS may, in its Technical Conditions for Connecting to the Grid, require current asymmetry higher than 2% provided that this does not hinder access of other users to the transmission system, i.e. that it does not violate the preconditions for normal operation of the power system. 31 4.2.7.2. Higher harmonics 4.2.7.2.1. The higher harmonic currents generated by the facility of transmission system user at its connecting point in 110 kV and 220 kV grids must not exceed values: nom s n hn U S k I 3 where: Ihn – n harmonic current; kn – coefficient factor of n harmonic (determined in accordance with the Table 4.1); Ss – max apparent power at the connection/interconnection point (calculated based on allowed power demand and power factor) in case that it is less than 5% of apparent power of three phase short-circuit connection, otherwise Ss is 5% of the apparent power of three phase short-circuit connection; Unom – nominal voltage of the transmission grid at the connection/inter-connection point. 4.2.7.2.2. If the facility is connected to the 400 kV grid, the obtained values of currents Ihn from the point 4.2.7.2.1. are multiplied by 0.6. Table 4.1 No. of odd harmonic k n [%] No. of even harmonic k n [%] k n [%] 3 6.5 2 3 Total 8 5 and 7 8 2 1.5 40 2 2 n n g k Т 9 3 4 1 11 and 13 5 13 3 Download 0.65 Mb. Do'stlaringiz bilan baham: |
Ma'lumotlar bazasi mualliflik huquqi bilan himoyalangan ©fayllar.org 2024
ma'muriyatiga murojaat qiling
ma'muriyatiga murojaat qiling