“Branches” worksheet 
The “Branches” worksheet is for source and result data on network model branches (lines) and 
transformers. 
Nhead 
Head bus indentifier 
1
Injection is difference between generation and load values. 
2
Computational Methods for Large Sparse Power Systems Analysis. S.A. Soman, S.A. Khaparde, Shubha Pandit, 2001 



Ntail 
Tail bus identifier 
Nparr 
Number of parallel line to identify unique branch. Can be zero for single branch between 
head and tail buses. 
Name 
Branch name. This field is filled automatically with respect to names of head and tail bus-
es. 
State 
State of branch. Can be “on” and “off”. 

Real part of branch resistance in Ohms. Can be zero. 

Imaginary part of branch resistance in Ohms. Can be zero or negative. 

Real part of ground conductance in 𝝁Sm. Positive number means active power consump-
tion. 

Imaginary part of ground conductance in 𝝁Sm. Negative number means reactive power 
generation (conductance shunt), positive – reactive power consumption (inductance 
shunt). 
Ghead 
Auxiliary real part conductance at the head of branch in 𝝁Sm. 
Bhead 
Auxiliary imaginary part of conductance at the head of branch in 𝝁Sm. 
Gtail 
Auxiliary real part conductance at the tail of branch in 𝝁Sm. 
Btail 
Auxiliary imaginary part of conductance at the tail of branch in 𝝁Sm. 
Kt 
Real part of transformer ratio. Ratio is defined as result of division of voltage magnitude 
at tail bus of the branch by voltage magnitude at head bus. If Kt is zero or empty, InorXL 
will treat it as unity. 
iKт 
Imaginary part of transformer ratio. It is ratio, not angle shift between voltage phasors ! 
Phead 
Calculated active power flow at head of branch in MW. 
Qhead 
Calculated reactive power flow at head of branch in MVar. 
Ptail 
Calculated active power flow at tail of branch in MW. 
Qtail 
Calculated active power flow at tail of branch in MVar. 
Depending on transformer ratio, branch model can be represented as power transmission line 
model or power transformer model.
For Kt = 1: 
For Kt ≠ 1: 



Difference is in the way of shunt part modeling. Ordinary branch with Kt=1 has shunt conduct-
ance divided equally between head and tail buses. Transformer branch with Kt≠1 has whole shunt con-
ductance at head bus. 
Auxiliary conductances are introduced for compatibility with “RastrWin” branch model. These 
conductances refers to “RastrWin” line reactors. Each reactor has conductance 𝐺
0
+ 𝑗𝐵
0
. After import-
ing load flow case from “RastrWin” Ghead, Bhead, Gtail and Btail will be filled with equivalent values 
referred to line reactors: 𝑛(𝐺
0
+ 𝑗𝐵
0
). If your case created with InorXL these conductances may be ig-
nored. 
Branch may have zero or negative reactances. In theory, negative reactances leads to conver-
gence problems, but in most cases InorXL can take workarounds with such parameters. 
When load flow calculation is successfully completed, Phead, Qhead, Ptail and Qtail columns will 
be filled with calculated power flows. Power flows are calculated at points “just near” bus connection, as 
shown by metering transformers symbols at figure above. 
Resistance of transformer branches refers to head bus voltage. Shunt conductance 𝐺
𝑡𝑎𝑖𝑙
+ 𝑗𝐵
𝑡𝑎𝑖𝑙
refers to tail bus and will not be modified with respect to voltage magnitude.  