Carbon Dioxide t ransmitters air quality the Series cdw wall Mount Carbon Dioxide/Temperature Transmitter
Download 16.49 Kb. Pdf ko'rish
|
- Bu sahifa navigatsiya:
- SPECIFICATIONS Range
- Ambient Operating Temperature
- Weight
- Model CDW
- Response Time
- Outputs
CALL TO ORDER: U.S. Phone 219 879-8000 • U.K. Phone (+44) (0)1494-461707 • Australia Phone (+61) (0) 2 4272 2055 147
Carbon Dioxide T ransmitters AIR QUALITY The Series CDW Wall Mount Carbon Dioxide/Temperature Transmitter combines accurate CO2 measurements with a passive temperature output. The Non- Dispersive Infrared (NDIR) sensor continuously updates the calibration through a proprietary logic feature which limits the amount of error due to drift. The CDW series is ideal for building automation systems to help control the fresh air intake in a room.
2 . Accuracy: ±100 PPM @ 22°C. Temperature Dependence: 0.2% FS per °C stability < 2% of FS mover life of sensor.
reading per mm of Hg. Response Time: 3 to 5 minutes for 90% step change. Ambient Operating Temperature: 32 to 122°F (0 to 50°C). Storage Temperature: -4 to 158°F (-20 to 70°C). Power Requirements: 18 - 30 VAC RMS 50/60 Hz, 18 to 42 VDC polarity protected.
average 3.25 VA peak. Sensor: Non-dispersive infrared sensor.
Output: 0 to 10 VDC for CO 2 ; 20K ohm NTC thermistor for temperature. Weight: 0.5 lb (227 g). Agency Approval: CE. Series CDW Wall Mount Carbon Dioxide/Temperature Transmitter Measure up to 2000 PPM, NDIR Sensor 3-7/32 [81.76]
1-5/64 [27.61]
1-1/4 [31.75]
1-9/32 [32.51]
1/4 [6.35]
19/32 [15.14]
3-35/64 [90.04]
3-31/32 [100.84]
4-5/8 [117.48]
CL 6 6 Model CDW, Wall Mount CO 2 /Temperature Transmitter Model CDW-LED, Standard Model with LED Option Duct Mount Carbon Dioxide Transmitter NDIR Sensing Technology, 2000 PPM Range
in a room by detecting the concentration of carbon dioxide in the return air duct. The non- dispersive infrared sensing technology automatically updates the calibration of the transmitter using a proprietary logic feature which limits the amount of error due to drift. The Model CDD can measure up to 2000 PPM in duct air flows less than 1500 FPM.
@ 22°C.
Temperature Dependence: 0.2% FS per °C.
Stability: < 2% of FS over life of sensor.
Non-Linearity: < 1% of FS. Pressure Dependence: 0.13% of reading per mm of Hg. Response Time: 3 minutes typical for 90% step change. Duct Air Velocity Range: 0 to 1500 FPM (7.63 m/s). Ambient Operating Temperature: 32 to 122°F (0 to 50°C). Storage Temperature: -4 to 158°F (-20 to 70°C). Power Requirements: 18 to 30 VAC RMS 50/60 Hz or 18 to 42 VDC. Power Consumption: 1.65 watts peak (0.65 watts average at 42 VDC). Outputs: 0 to 10 VDC. Housing: Flammability classification UL rated 94V-5VA. Weight: 8 oz (230 g). 1-39/64
[40.88] 3-1/32
[77] 1-1/8
[28.58] 4-1/8
[104.78] ø1-1/4
[ø31.7] 4X KNOCKOUT 1/2˝ CONDUIT HOLE 2X Ø7/32 [2X Ø5.56] 3-1/16 [77.79]
4-31/32 [126.21]
5-11/16 [144.46]
Model CDD, Carbon Dioxide Transmitter 147.P.N:Layout 2 7/22/10 2:13 PM Page 1 Katalog: wp-content -> uploads -> 2013 2013 -> Atandosh vatandin yaxshi yor bo‘lmas! 2013 -> The state of urban food insecurity in cape town 2013 -> The invisible crisis: urban food security in southern africa 2013 -> Recapiti patronato acli/ caf albese con Cassano 2013 -> Monarchy: The Czar (Tsar) Download 16.49 Kb. Do'stlaringiz bilan baham: |
ma'muriyatiga murojaat qiling