Abb totalFlow Interface Reference


Download 203.85 Kb.
Pdf ko'rish
bet12/17
Sana03.11.2023
Hajmi203.85 Kb.
#1743270
1   ...   9   10   11   12   13   14   15   16   17
Bog'liq
ABB TotalFlow Interface Reference EPDOC-X340-en-501A

Property
Description
Diagnostic
Address
The valid address in the controller to read for the diagnostic scan.
Character
Timeout
The maximum interval between receipts of characters (bytes). If
this time is exceeded, the Toolkit assumes the incoming data
stream was broken. The value must be between
1
and
60
seconds,
with the default value being
2
seconds.
Compressed
Indicates whether compression is enabled. The default value is
unselected.
Time
Synchronization
Enable at
If selected, time synchronization is enabled for the device. The
default is not selected (disabled).
Type the time (in 24–hour format:
HH:SS
) at which synchronization
will occur. The default value is midnight (
00:00
).
Item Type
The type of controller specified when this item was created.
Last Modified
The date and time the controller properties were modified.
Last
Downloaded
The date and time the controller was last downloaded to the
server.
Item Number
The unique item number currently assigned to this controller, in
the format
RTUnnnnn
.
You can change the item number if you need to match your
current server database configuration. The number must be
between
00001
and the maximum number of controllers allowed
for your system. For more information about setting the maximum
value, see the topic titled "Adjusting sizing of non-licensed items"
in the Supplementary Installation Tasks Guide. Note that the
maximum number of controllers that may be used in a system is
defined in the Experion specification for that Experion release,
This number is likely to be less than the maximum number that
can be configured in the database as shown in "Adjusting sizing of
non-licensed items."
About time synchronization on ABB Totalflow
controllers
Time synchronization is critical when you use EFM. Some controllers
have their own GPS-based time source or use NTP over TCP/IP to
Chapter 2 - ABB Totalflow channel and controller reference


synchronize their time, in which case you do not need to synchronize
using the ABB Totalflow interface.
Experion performs time synchronization with ABB Totalflow
controllers at the time specified in the controller settings.
Optimizing ABB Totalflow scanning
performance
An ABB Totalflow scan packet:
n
Can contain multiple register requests. Each register request is a
combination of Application | Table | Index | Range.
n
Must have addresses with the same scan period, unless dynamic
scanning is enabled.
The Totalflow protocol is able to request blocks of parameters, so
keeping indexes in the same table that are adjacent to each other on
the same scan period will help reduce the number of requests.
Alternatively, you can enable
Dynamic Scanning
on the controller and
Experion will optimize the scanning.
Two types of scan packet are built for ABB Totalflow:
n
Hardware Diagnostic
. One scan per controller at a defined regular
interval (the default is 60 seconds) to verify communications
integrity with the controller. This scan packet is automatically
created to scan the diagnostic address configured for the
controller.
n
Periodic Data Acquisition
. A defined regular interval in which the
server database acquires information from the addressed registers
in the controller and processes the values as point parameters.
You need to define the scan period for each point parameter
source address. The scan period should reflect both the rate at
which the value held in memory changes and its importance to the
process (critical or non-critical).
There is one periodic data acquisition scan per scan packet.
Configuring RTU credentials for an ABB
Totalflow controller
rtucredentials
is a command line utility that enables you to provide
credentials for the ABB Totalflow controller.
22
Chapter 2 - ABB Totalflow channel and controller reference


23
If you do not enter your credentials, connection to the controller
and/or channel cannot be guaranteed meaning that no data will be
able to be scanned from the device.
To configure RTU credentials for an ABB Totalflow
controller
1. On the primary server, open a
Command Prompt
window.
2. Type
rtucredentials
to start the RTU Credentials utility.
3. Type the number of the first controller to be configured
For example,
25
for
controller 25
.
4. Type the number of the last controller to be configured
For example,
25
for
controller 25
.
The message
Setting credentials for Controller n
appears, where
n
is
the controller number, or numbers, specified.
5. Type your 4–digit security code when prompted, and then press
Enter
.
The message
Completed processing credentials for Controller n
appears, where
n
is the controller number, or numbers, specified.