Chapter-7 Fire Protection and Fire Safety Requirements
a)
All buildings of 24 m. and above in height, except group housing and 45 m.
and above in case of apartment /group housing society building.
b)
Hotels below l5 m. in height and above 1000 sq m. built
up area at each floor
and or if basement is existing.
c)
All hotels, mercantile, and institutional buildings of 15 m. and above.
d)
Mercantile building having basement more than one floor but below 15 m.
(floor area not exceeding 750 sq m.)
e)
Underground Shopping Complex.
f)
Underground car / scooter parking /enclosed car parking.
g)
Basement area 200 sq m. and above.
h)
Any special hazards where the Chief Fire Officer considers it necessary.
i)
For buildings up to 24 m. in height where automatic
sprinkler system is not
mandatory as per these Bye-Laws, if provided
with sprinkler installation
following relaxation may be considered.
i) Automatic
heat/smoke
detection
system and M.C.P. need not be
insisted upon.
ii)
The number of Fire Extinguisher required shall be reduced by half.
7.23 FIXED CARBON DI-OXIDE / FOAM / DCO WATER SPRAY
EXTINGUISHING SYSTEM
Fixed extinguishing installations shall be provided as per the relevant specifications in the
premises where use of above extinguishing media is considered
necessary by the Chief Fire
Officer.
7.24
FIRE ALARM SYSTEM
All buildings of 15 m. and above in height shall be equipped
with fire alarm system, and also
residential buildings (Dwelling House, Boarding House and Hostels) above 24 m. height.