Chapter-7 Fire Protection and Fire Safety Requirements
7.25
CONTROL ROOM
There shall be a control room on the entrance floor of the
building with communication
system (suitable public address system) to all floors and facilities for receiving the message
from different floors. Details of all floor plans along with the
details of fire fighting
equipment and installation shall be maintained in the Control Room. The Control Room shall
also have facility to detect the fire on any floor through indicator
boards connecting fire
detection and alarm system on all floors. The staff in charge of the Control Room shall be
responsible for the maintenance of the various services and
fire fighting equipment and
installation. The Control Room shall be manned round the clock by trained fire fighting staff.
7.26
FIRE DRILLS AND FIRE ORDERS
The guidelines for fire drill and evacuation etc. for high-rise
building may be seen in
Appendix (B) of National Building Code part IV. All such building shall prepare the fire
orders duly approved by the Chief Fire Officer.
7.27
A qualified fire officer and trained staff shall be
appointed for the following
buildings.
a)
All high rise buildings above 30 m. in height where covered area of one floor
exceeds 1000 sq m. except apartments / group housing.
b)
All hotels, identified under classification three
star and above category by
Tourism Department and all hotels above 15 m. in height with 150 beds
capacity or more without star category.
c)
All hospital building of 15 m. and above or having number of beds exceeding
100.
d)
Underground shopping complex where covered area exceeds 1000 sq m.
e)
All high hazard industries.
f)
Any other risk which Chief Fire Officer considers necessary.