Chapter-7 Fire Protection and Fire Safety Requirements
6
Unless otherwise specified in Bye-Laws, the
fire fighting equipments
/installation shall conform to relevant Indian Standard Specification.
7
In case of mixed occupancy, the fire fighting arrangement shall be made as
per the highest class of occupancy.
8
Requirement of water based first aid fire extinguishers
shall be reduced to half
if hose reel is provided in the Building.
7.21
STATIC WATER STORAGE TANK
a)
A satisfactory supply of water exclusively for the purpose of fire fighting shall
always be available in the form of underground
static storage tank with
capacity specified in Annexure-A with arrangements of replenishment by
town's main or alternative source of supply @ 1000 liters per minute. The
static storage water supply required for the above mentioned purpose should
entirely be accessible to the fire tenders of the local fire service.
Provision of
suitable number of manholes shall be made available for inspection repairs
and insertion of suction hose etc. The covering slab shall be able to withstand
the vehicular load of 45 tonnes in case of high rise and 22
tonnes in case of
low rise buildings. A draw off connection shall be provided. The slab need not
strengthened if the static tank is not located in mandatory set- back area.
b)
To prevent stagnation of water in the static water tank the suction tank of the
domestic water supply shall be fed only through
an over flow arrangement to
maintain the level therein at the minimum specified capacity.
c)
The static water storage tank shall be provided with a fire brigade collecting
branching with 4 Nos. 63mm dia instantaneous male inlets arranged in a valve
box with a suitable fixed pipe not less than 15 cm dia
to discharge water into
the tank. This arrangement is not required where down comer is provided.