6.1
Example M&V Plan
The following figure will help illustrate the savings verification process:
Figure 5-1
Chiller Performance and Savings
400
kW New
kW Baseline
ASHRAE model for
baseline chiller
kW measured
2. Estimate baseline chiller
300
1. Measure chiller load and
operating conditions.
demand at standard conditions.
Manufacturer's model for
new chiller
4. Calculate kW reduction as
difference between baseline
and measured values.
200
kW
3. Measure the new chiller
demand.
100
0
0
100
200
300
400
Tons
1. Measure the chiller load (tons) from the chilled water supply and return temperatures
and flow rates.
2. Estimate the baseline kW demand from the model of the old chiller at current
operating conditions (actual chilled water temperature, tons). The baseline condenser
water temperature will be held 85ºF since that was the steady-state case in the
baseline due to the old chiller’s operating limitations).
3. Measure the new chiller demand under actual operating conditions.
4. Calculate the demand savings for each 15-minute interval as the difference between
the baseline model and the measured value.
5. If the chiller is off, demand reduction is treated as 0 kW.
6. Annual energy savings will be calculated as the sum of the 15-minute savings. This
savings calculation assumes a minimum number of ton-hours of cooling per year. In
the event that the measured ton-hours are less than a specified minimum, savings
based on measured chiller performance may be adjusted upwards to reflect what
would have occurred had the minimum number of ton-hours been provided.
2/07
page 22