6.1
Example M&V Plan
chiller could not take advantage of reduced condenser water temperatures because of
physical operating limitations.
5.3 Proposed Energy and Water Savings Calculations and
Methodology
The energy and demand savings will be calculated using Equations 5-7 and 5-8,
respectively.
Equation 5-7
Energy Savings (kWh) =
Σt (kWh
t
,
baseline, est
– kWh
t
,
measured, post
)
= 0.25
× Σt (kW
t, baseline
–kW
t,measured post
)
Where:
kW
t,baseline
=
demand that the baseline chiller would have used
under the load conditions encountered for 15minute
interval t in the post-installation period
kW
t, measured, post
=
measured demand of the new chiller during 15
minute interval t.
Equation 5-8
Monthly Demand Savings (kW) = MAX(kW
t,baseline
) – COINCIDENT(
kWt,post
)
Where:
MAX(kW
t,baseline
)
=
maximum monthly demand of baseline
chiller predicted for each 15-minute interval
in the peak period (between noon and 6 p.m.
weekdays, May through October) during the
current month using the model developed
for the baseline chiller.
COINCIDENT(kW
t,post
)
=
measured demand of the new chiller during
the period when the predicted baseline
chiller demand was at its maximum value.
Annual cost savings will be calculated using Equation 5-9.
Equation 5-9:
Annual Cost Savings = Energy Savings (kWh) * Rate
kWh
+
Σmonth(Monthly Demand Savings * Rate
kW
)
where the rates are detailed in Table 2-1 in Section 2.2.
2/07
page 25