Loyiha uchun berilganlar 8


Ilovalar Yuklama borligida kuchlanishi rostlanadigan uch fazali transformatorlarning texnik ko‘rsatkichlari


Download 0.84 Mb.
bet12/12
Sana06.10.2023
Hajmi0.84 Mb.
#1693676
1   ...   4   5   6   7   8   9   10   11   12
Bog'liq
Loyiha uchun berilganlar 8

Ilovalar

Yuklama borligida kuchlanishi rostlanadigan uch fazali transformatorlarning texnik ko‘rsatkichlari.


I1-jadval.


Turi


Quvvati kVA

Transformtaor chulg‘amining nominal kuchlanishi, kV, va rostlanish chegarasi, %

uk



%

Transformator chulg‘ami-ning ulanish chizmasi va guruhi

Yuqori
kuchlanish



Past kuchlanish

kV

%

kV

%

1.

TMN-6300/35

6300

35

9

6,3

10,5

7,5

Y/Δ-1

2.

TMH-6300/110

6300

115

16

6,6

11,0

10,5

Y/Δ-3

3.

TDN-10000/35

10000

35

12

6,3

10,5

8,0

Y/Δ-5

4.

TDN-10000/110

10000

115

16

6,6

11,0

10,5

Y/Δ-7

5.

TDN-16000/35

16000

35

12

6,3

10,5

10,5

Y/Δ-9

6.

TDN-16000/110

16000

115

16

6,6

11,0

10,5

Y/Δ-11

7.

TRDN-25000/35

25000

35

12

6,3/6,3

10,5/10,5

10,5

Y/Δ-9

8.

TRDN-25000/110

25000

115

16

6,3/6,3

10,5/10,5

10,5

Y/Δ-7

9.

TRDN-40000/230 110

10000

230/115

16

6,3/6,3

10,5/10,5

10,5

Y/Δ-5

10.

TRDN-63000/230 110

63000

230/115

16

6,3/6,3

10,5/10,5

10,5

Y/Δ-3

ESLATMA:

  1. TRDN tipidagi quvvati 25 MVA va undan ortiq bo‘lgan transformatorlarning past kuchlanish chulg‘ami parchalangan / ikkita bir xil qismdan iborat / bo‘ladi.

  1. Transformatorlar RPNlarining rostlash chegaralari quyidagicha:

a/ 35 kV li Str.nom =6,3 MVA uchun 6x 1,5 %
Str.nom = 10 ÷ 16 MVA uchun 8x 1,5
b/ 110 kV li tarnsformatorlar uchun 9x 1,78%

6-10/0, 69-0,4 kV li sex transformatorlarning texnik ko‘rsatkichlari
I2-jadval.

TiP

ST kVA


Chulg‘amlarning
kuchlanishi, kV

uq



%

Transformator 2chulg‘ami-ning chizmasi va ulanish guruhi

YuK



PAST Kuchlanish

TM-630/10

630

6,0/10,5

0,4-0,23

5,5




TM-630/10

630

6,0/10

0,69-0,4

5,5




TMZ-1000/10

1000

6,0/10

0,4-0,23

5,5

Δ/ Y -12

TMZ-1600/10

1600

6,0/10

0,4-0,23

5,5

Yoki

TMZ-1600/10

1600

6,0/10

0,69-0,24

5,5

Δ/ Y -11

TMZ2500/10

2500

6,0/10,0

0,4-0,23

5,5




TMZ-2500/10

2500

6,0/10,0

0,69-0,4

5,5






Kuchlanishi 6 va 10 kV li asinxron va sinxron dvigatellarning texnik ko‘rsatkichlari
I3-jadval.

Dvigatel tipi

Rn, kVT

Un, kV

Unom, A

kyu

Sosφn

ATD-800-4

800





5,6

0,90

ATD-1000-6

1000





6,2

0,90

ATD-1250-2

1250





6,2

0,90

AKN-1600-4

1600





6,5

0,91

AKN-2000-6

2000





6,5

0,91

STD-630-2

630





6,7

0,9

STD-1000-2

1000





6,7

0,90

STD1250-4

1250





6,5

0,9

STD-1600-2

1600





6,8

0,90

STD-2000-2

2000





7,0

0,90

STD-2500-2

2500





6,2

0,90


FOYDALANILGAN ADABIYOTLAR


1) " Elektr ta'minoti tizimining rele himoyasi va avtomatikasi " A.M.Qosimahunova , I.X.Siddiqov . Farg'ona . " Aloqachi " 2021 .
2). Rele himoyasi va avtomatitka fanidan kurs ishini bajarish uchun uslubiy qo'llanma . FarPl .: 2019 yil .
3). Aндpеев B.A. Релейная зашита и автоматика систем электроснабжения : учебн . я вузов по сHес . Электроснабжение . M .: Высш шк . 1991.
4). Illaбад M.A. Расчеты релейиой зашиты и автоматики распределителныX сетей . Энергоавтоматиздат . 1985.
5). Ilравила експлуатасии электроустановок потребителей . СП16 .: издателство « < / leaн >> . 2000. 320c .



Download 0.84 Mb.

Do'stlaringiz bilan baham:
1   ...   4   5   6   7   8   9   10   11   12




Ma'lumotlar bazasi mualliflik huquqi bilan himoyalangan ©fayllar.org 2024
ma'muriyatiga murojaat qiling