Static Electricity 2000 Edition
Download 1.59 Mb. Pdf ko'rish
|
NFPA 77 Static Electricity
- Bu sahifa navigatsiya:
- 6.3 Control of Static Charge Generation.
- 6.4 Charge Dissipation. 6.4.1 Bonding and Grounding.
- FIGURE 6.4.1 Bonding and grounding. 6.4.1.1
6.2.4 Relocating Equipment.
Where equipment that can accumulate a static electric charge is unnecessarily located in a hazardous area, it might be possible to relocate it to a safe location rather than to rely on other means of hazard control. 6.3 Control of Static Charge Generation. Electric charges separate when materials are placed in contact and are pulled apart. Reducing process speeds and flow rates will reduce the rate of charge generation. Examples of such charge separa- tion are found where plastic parts and structures, insulating films and webs, liquids, and particulate material are handled. If the material flows at a slow enough rate, a hazardous level of excess charge will not normally accumulate. This means of W 1 2 ---CV 2 = W 1 2 --- Q 2 C ------ = 77– 14 STATIC ELECTRICITY 2000 Edition static electricity control might not be practical due to process- ing requirements. (See Chapters 7 through 9 for recommended prac- tices in specific applications.) 6.4 Charge Dissipation. 6.4.1 Bonding and Grounding. Bonding is used to minimize the potential difference between conductive objects, even when the resulting system is not grounded. Grounding (i.e., earthing), on the other hand, equalizes the potential differ- ence between the objects and the earth. The relationship between bonding and grounding is illustrated in Figure 6.4.1. FIGURE 6.4.1 Bonding and grounding. 6.4.1.1 A conductive object can be grounded by a direct con- ductive path to the earth or by bonding it to another conduc- tive object that is already connected to the ground. Some objects are inherently bonded or inherently grounded because of their contact with the ground. Examples of inher- ently grounded objects are underground metal piping or large metal storage tanks resting on the ground. 6.4.1.2 The total resistance between a grounded object and the soil is the sum of the individual resistances of the ground wire, its connectors, other conductive materials along the intended grounding path, and the resistance of the ground electrode (i.e., ground rod) to the soil. Most of the resistance in a ground connection exists between the ground electrode and the soil. This ground resistance is quite variable, since it depends on the area of contact, the resistivity of the soil, and the amount of moisture present in the soil. 6.4.1.3 To prevent the accumulation of static electricity in con- ductive equipment, the total resistance of the ground path to earth should be sufficient to dissipate charges that are other- wise likely to be present. A resistance of 1 megohm (10 6 ohms) or less is generally considered adequate. Where the bonding/ grounding system is all metal, resistance in continuous ground paths will typically be less than 10 ohms. Such systems include multiple component systems. Greater resistance usually indi- cates the metal path is not continuous, usually because of loose connections or corrosion. A grounding system that is accept- able for power circuits or for lightning protection is more than adequate for a static electricity grounding system. Appendix C contains diagrams of various grounding devices, connections, and equipment. 6.4.1.4 Where wire conductors are used, the minimum size of the bonding or grounding wire is dictated by mechanical strength, not by its current-carrying capacity. Stranded or braided wires should be used for bonding wires that will be connected and disconnected frequently. (See Appendix C for additional information.) 6.4.1.5 Grounding conductors can be insulated (e.g., a jack- eted or plastic-coated cable) or uninsulated (i.e., bare conduc- tors). Uninsulated conductors are recommended, because it is easier to detect defects in them. 6.4.1.6 Permanent bonding or grounding connections can be made by brazing or welding. Temporary connections can be made using bolts, pressure-type ground clamps, or other spe- cial clamps. Pressure-type clamps should have sufficient pres- sure to penetrate any protective coating, rust, or spilled material to ensure contact with the base metal. 6.4.1.7 Workers should only be grounded through a resis- tance that limits the current to ground to less than 3 mA for the range of voltages experienced in the area. This method is called soft grounding and is used to prevent injury from an elec- tric shock from line voltages or stray currents. Download 1.59 Mb. Do'stlaringiz bilan baham: |
Ma'lumotlar bazasi mualliflik huquqi bilan himoyalangan ©fayllar.org 2024
ma'muriyatiga murojaat qiling
ma'muriyatiga murojaat qiling