7.11 Gauging and Sampling.
Gauging and sampling opera- tions, including temperature measurement, can introduce spark promoters into a storage tank or compartment. It is rec- ommended that a conductive gauging well for manual sam- pling and gauging be used. The precautions given in Section 7.11 should be taken where use of a gauging well is not possi- ble, where the material stored is a nonconductor, or where the vapor space of the container could be ignitible. Where these operations are conducted manually, the personnel grounding recommendations of Section 6.6 should be considered. 7.11.1 Materials. Gauging and sampling systems should be either completely conductive or completely nonconductive. For example, conductive sampling and gauging devices should be used with a conductive lowering device, such as a steel tape or cable. Chains are not electrically continuous and should not be used in flammable atmospheres. Conductive sampling and gauging devices, including the sampling con- tainer and lowering device, should be properly bonded to the tank or compartment. Such bonding should be accomplished by use of a bonding cable or by maintaining continuous metal- 77– 24 STATIC ELECTRICITY 2000 Edition to-metal contact between the lowering device and the tank hatch. Ideally, if nonconductive hand gauging or sampling devices are used, no waiting period is required after loading or filling. However, it should be noted that these devices might not retain the necessary level of nonconductivity due to envi- ronmental factors such as moisture or contamination. There- fore, an appropriate waiting period is also recommended when nonconductive devices are used. Cord made from synthetic material such as nylon should not be used due to possible charging if it slips rapidly through gloved hands. Although natural cellulosic fiber cord can, in principle, be used, it is found that such cord is frequently com- posed of a natural synthetic blend, with corresponding charge generating ability. 7.11.2 Gauging. Where possible, gauging should be carried out with automatic gauging systems. These can be used safely in tanks, provided the gauge floats and similar devices are elec- trically bonded to the tank shell through a conductive lead-in tape or conductive guide wires. Free-floating, unbonded floats can be effective spark promoters and should be avoided. Non- contact gauging devices, such as radar and ultrasonic gauges, are also satisfactory, provided electrical continuity is ensured. Isolated conductive components must be avoided. Download 1.59 Mb. Do'stlaringiz bilan baham: |
Ma'lumotlar bazasi mualliflik huquqi bilan himoyalangan ©fayllar.org 2024
ma'muriyatiga murojaat qiling
ma'muriyatiga murojaat qiling