7.19 SAFETY 
MEASURES 
IN 
ELECTRIC SUB-STATION 
1) 
Clear independent approach to the sub-station from outside the building shall 
be made available round the clock
2) 
The approaches/corridors to the sub-station area shall be kept clear for 
movement of men and material at all times.
3) 
The sub-station space is required to be provided with proper internal lighting 
arrangements.
4) 
In addition to natural ventilation proper ventilation to the sub-station area is to 
be provided by grill shutters and exhaust fans at suitable places so as to 
discharge all smoke from the sub-station without delay in case of fire so that 
sub-station operations can be carried out expeditiously.
5) 
Cable trenches of 0.6 m. X 0.6 m. dummy floor of 0.6 mt. depth shall be 
provided to facilitate laying of cable inside the building for connecting to the 
equipment.
6) 
Steel shutters of 8’X 8’ with suitable grills shall be provided for transformers 
and sub-station room.
7) 
The floor of the sub-station should be capable of carrying 10 tons of 
transformer weight on wheels.
8) 
Built up substation space is to be provided free of cost.
9) 
Sub-station space should be clear from any water, sewer, air conditioning, and 
gas pipe or telephone services. No other service should pass through the sub 
station space or the cable trenches.
10) 
Proper ramp with suitable slope may be provided for loading and unloading of 
the equipment and proper approach will be provided.
11) 
RCC pipes at suitable places as required will be provided for the cable entries 
to the sub station space and making suitable arrangement for non-ingress of 
water through these pipes.
12) 
The sub station space is to be provided in the approved/sanctioned covered 
area of the building.