I elektr yuklamalarini hisoblash. 5 II. Kuch transformatorini quvvati va sonini aniqlash 18


Download 244.85 Kb.
bet1/2
Sana12.01.2023
Hajmi244.85 Kb.
#1089747
  1   2
Bog'liq
Saidjafar akaxon (2)


Mundarija

Xulosa 29

KIRISH 2
I.ELEKTR YUKLAMALARINI HISOBLASH. 5
II.KUCH TRANSFORMATORINI QUVVATI VA SONINI ANIQLASh 18
III.TEXNIK – IQTISODIY QIYOSLASH NATIJASIDA ELEKTR STANTSIYALARI VA PODSTANTSIYALARINI BOSH SXEMASINI TANLASH………………………………………………………………………..22
IV.QISQA TUTAShUV TOKLARNI HISOBLASh 23
V. ELEKTROSTANTSIYA VA PODSTANTSIYALARDA ASBOB – USKUNALARNI TANLASH 27
Hulosa 29
Adabiyotlar 30

KIRISh.



Bugun mamlakatimizni modernizatsiya kilish va yangilash, iqtisodiyotimizning sifat jixatidan yangi, zamonaviy tarkibiy tuzilmasini shakllantirish, xududlarimizni kompleks rivojlantirish bo‘yicha barcha rejalarimizning muvaffakiyatli amalga oshirilishi infratuzilma tarmoklarini yuksak sur’atlar bilan rivojlantirishga uzviy bog‘lik ekani xakida gapirishning xojati yo‘k.
Infratuzilmani rivojlantirish bo‘yicha kabul kilingan dasturlarda yakin istikbolda yangi energetika kuvvatlarini, elektr energiyasini uzatish tarmoklarini barpo etish va mavjudlarini rekonstruksiya kilish bo‘yicha 26 tadan ortik investitsiya loyixasini amalga oshirish ko‘zda tutilgan. Bular, avvalambor, Tallimarjon issiklik elektr stansiyasida umumiy kuvvati 900 megavolt bo‘lgan ikkita bug‘-gaz kurilmasini, Toshkent issiklik elektr stansiyasida kuvvati 370 megavoltni tashkil etadigan bug‘-gaz kurilmasini, Angren issiklik elektr stansiyasida kuvvati 130-150 megovattdan iborat energoblokni, Farg‘ona vodiysida yangi energetika kuvvatlarini barpo etish, Sirdaryo va Yangi Angren issiklik elektr stansiyalarini bir-biri bilan bog‘laydigan yukori voltli elektr uzatish tarmog‘ini kurish, Ustyurt gaz-kimyo majmuasining tashki energiya ta’minotini tashkil etish kabi muxim strategik loyixalardir.
Ayni loyixalash ishlarini amalga oshirishda kurs ishini amalga oshirish yuqoridagi ulkan ishlarni ro‘yobga chiqarishda ilk qadamlar bo‘ladi.
Kurs ishi topshirig‘ida quyidagilar ko‘rsatilgan :
a) energetik tizim haqida ma’lumot;
b) yig‘ma shinalardagi maksimal quvvat, /MVt/;
v) energetik tizimni kuchlanishi In /kV/;
g) chiqish liniyalarining soni va kuchlanishi;
d) elektr stansiyalari yoki podstansiyani tipi va iste’molchilarining turi.
Topshiriqni amalga oshirishda talaba oldinga qo‘yilgan masalani nazariy va amaliy bilimlariga tayanib yoritish uchun ko‘nikma xosil qiladi.
Energiya tizimi bilan aloqa va ortiqcha quvvatni berish 110, 220 yoki 330 kV kuchlanishli kuchlanishda amalga oshiriladi, buning uchun stansiyada yuqori kuchlanishli o'tkazgichlar qurilmoqda. GRU aloqa transformatorlari orqali yuqori kuchlanishli elektr uzatish moslamalariga ulanadi. Odatda, ikkita ulash transformatori o'rnatiladi, ular stansiyaning turli ish rejimlarida barcha ortiqcha quvvatni berishni ta'minlashi kerak.
Yuqori issiqlik yuklari mavjud bo'lganda, CHESda katta quvvatli - 120 MVt va undan ko'p turbinali bloklar o'rnatiladi. Bunday quvvatli generatorlarning nominal kuchlanishlari 10 kV (15, 75; 18 yoki 20 kV) dan ortiq bo'lganligi sababli, ular kuchaytiruvchi transformatorlar bilan bloklarga ulanadi va 110-330 kV o'tkazgich shinalari elektr energiyasi bilan ta'minlanadi. Bunday holda, 6-10 kV iste'molchilar iste'molchi taqsimlash moslamasidan quvvatlanadi.
Iste'molchi KRU odatda ajratilgan seksiyali kalitlarga bo'lingan bir yoki ikkita shina tizimiga ega. KRU uchastkalari pastga tushiruvchi transformatorlar orqali ikkita stansiya generatoriga ulanadi.
So‘nggi yillarda mamalakatimizning Energetika tizimida amalga oshirilgan islohotlar natijasida bir yil ichida $2 mlrdlik to‘g ‘ridan-to‘g ‘ri investitsiya hisobiga 2700 MVt quvvatli 6 ta yangi elektr stansiyasini qurish bo‘yicha loyihalar boshlab yuborilgan.
Har bir kompaniyaga, shu jumladan, „Hududiy elektr tarmoqlari“ AJ oldiga ham bir qator vazifalarni qo‘ydi. Qilinadigan modernizatsiya, rekonstruksiya ishlarini amalga oshirishga tarifni ko‘tarish hisobidan emas, balki mana shu ishlab chiqarishda ketadigan harajatlarni, ya’ni tannarxni kamaytirish evaziga erishish masalasini yechimini choralari ko‘rilmoqda.
Yuqoridagi masalalarni davlatimiz rahbari tomonidan ham o‘z chiqishlarida takidlab o‘tganlar: “Davlat korxonalarini transformatsiya qilish bo‘yicha biz juda katta o‘zimizga majburiyat olganmiz, xalqimiz oldida. Hammamiz uchun bu — yangilik. Agar biz energetika sohasida transformatsiyani to‘g ‘ri qilsak, juda katta natijalarga erishishimiz mumkin. Eng katta narsa, bu — tannarxni kamaytirish. Qayerga bormasak, odamlar elektr energiyadan norozi. Hozirgi ko‘p elektr stansiyalarining eskirish darajasi 50 foizdan yuqori. Uch yil oldin 70 foiz edi. Bu albatta, raqobatbardoshlilik nuqtai nazaridan, harajat nuqtai nazaridan mutlaqo bizning hozirgi rejalarimizga to‘g ‘ri kelmaydi” — dedi davlat rahbari.
Shu bilan birga, prezident yangi tashkil etilgan to‘rtta mustaqil kompaniya — «O`zbekiston milliy elektr tarmoqlari», «Hududiy elektr tarmoqlari», «Issiqlik elektr stansiyalari» va «O`zbekgidroenergo» aksiyadorlik jamiyatlari transformatsiyaga tayyor yoki yo‘qligini aniqlash bo‘yicha vazifa bergan. Issiqlik stansiyalarida davlat xususiy sherikchilikni rivojlantirish boshlangani, biroq hududiy elektr stansiyalarda hali ham bu kechikayotgani tanqid qilingan.
“Bitta Sirdaryodagi ishlab chiqaradigan elektr energiyasi hududga yetib borguncha necha pulga tushayapti degan savol hammani qiynashi kerak. 4ta kompaniyani rahbari oldiga qo‘ygan vazifalarni qanday bajarish bo‘yicha aniq fikr aytishi kerak. Bular haftada 50 foiz ishini transformatsiya bilan shug ‘ullansa menga ham ma’qul”, — deya qayd etdi prezident.
Bundan kelib chiqadiki Energetika tizimini rivojlantirish davlat rivojlanish va istiqboli uchun eng zarur omillardan biri ekanligini davlat rahbari ham har bir yeg ‘ilishlarda qayta qayta takidlab o‘tmoqdalar.
Hozirgi kunda energiya ishlab chiqarish quvvatlarini oshirish va elektr energiyasi tannarxini kamaytirish choralari ko‘rilmoqda.Eleketr energiyasini sifatli va tannarxini kamaytirish chorasi sifatida mamlakatimizning gidroenergetik rejalari tuzildi:
2026 yilgacha O`zbekistonda umumiy quvvati 740 MVt bo‘lgan 21 ta gidroenergetika loyihasi ishga tushiriladi.
Kelgusi yildayoq 3 ta yangi GESning ishga tushirilishi va 4 ta mavjud GESning modernizatsiya qilinishi, gidroenergetika quvvatini 173 MVtga oshiradi. Toshkent viloyatining Bo‘stonliq tumanida kattaligi bo‘yicha Chorvoq GESidan keyin respublikada ikkinchi o‘rinda turadigan GES qurilishi uchun Pskem daryosi to‘sib qo‘yildi. Pskem suv ombori to‘g ‘onining balandligi 200 metrni tashkil qiladi. GES qurilishi loyihasi doirasida umumiy qiymati 799,6 million dollarlik investitsiyalarni o‘zlashtirish rejalashtirilgan. 418 MVt quvvatga ega Pskem GESi ishga tushirilgach, yiliga 950 million kVt•soat elektr energiyasi ishlab chiqaradi. 2026 yilga mo‘ljallangan yangi GESning ishga tushirilishi yiliga 250 million kub metr tabiiy gazni tejash imkonini beradi.

I. ELEKTR YuKLAMALARINI HISOBLASh.


Elektr yuklamalarini talab koeffitsenti K¬s buyicha hisoblaymiz. Sanoat iste'molchilari uchun talab koeffitsenti – Ks bildirgichlarda berilgan. (A-1).

  1. Berilgan sanoat korxonalari uchun aktiv quvvati quyidagi ifoda yordamida aniqlanadi.

[МVт] (1)
Рust – korxonaning berilgan aktiv quvvati (MVt)
Кs – talab koeffitsenti.
2. Yillik va bir sutkalik yuklamalarni grafigini qurish uchun quyidagilar aniqlanadi:
a) Xar bir sanoat korxonasi uchun to‘la va reaktiv quvvat:
[МVА] (2)
[МVаr] (3)
b) Bildirgich adabiyotlarda sanoat korxonalarining tipik grafiklari berilgan. (A.1). Bu tipik grafiklardan foydalanib, sanoat korxonalarini sutkalik va yillik grafiklari quriladi. Grafiklarni qurish uchun qish va yozgi kunlar uchun jadval tuziladi. Jadvalni tuzishda quyidagi ifodalardan foydalanamiz.


[MWt] (4)

Aholi yashash punkti uchun sutkalik aktiv quvvat jadvali




Qishki

Yozgi

Qishki

Yozgi




0_1

80

78

30,72

29,952




1_2

85

80

32,64

30,72




2_3

85

80

32,64

30,72




3_4

87

80

33,408

30,72




4_5

92

85

35,328

32,64




5_6

84

78

32,256

29,952




6_7

83

75

31,872

28,8




7_8

89

72

34,176

27,648




8_9

95

80

36,48

30,72




9_10

98

84

37,632

32,256




10_11

100

93

38,4

35,712




11_12

92

88

35,328

33,792




12_13

94

87

36,096

33,408




13_14

94

85

36,096

32,64




14_15

96

85

36,864

32,64




15_16

98

92

37,632

35,328




16_17

100

90

38,4

34,56




17_18

95

86

36,48

33,024




18_19

86

77

33,024

29,568




19_20

91

82

34,944

31,488




20_21

94

85

36,096

32,64




21_22

97

90

37,248

34,56




22-23

97

90

37,248

34,56




23_24

92

84

35,328

32,256













[MWt]

Neftni qazib olish uchun sutkalik aktiv quvvat jadvali




Qishki

Yozgi

Qishgi

Yozgi

0_1

95

80

47,88

40,32

1_2

90

80

45,36

40,32

2_3

88

80

44,352

40,32

3_4

90

80

45,36

40,32

4_5

92

88

46,368

44,352

5_6

91

85

45,864

42,84

6_7

90

85

45,36

42,84

7_8

92

87

46,368

43,848

8_9

98

87

49,392

43,848

9_10

100

95

50,4

47,88

10_11

100

95

50,4

47,88

11_12

98

95

49,392

47,88

12_13

96

93

48,384

46,872

13_14

97

93

48,888

46,872

14_15

99

93

49,896

46,872

15_16

99

93

49,896

46,872

16_17

96

90

48,384

45,36

17_18

98

90

49,392

45,36

18_19

98

90

49,392

45,36

19_20

96

88

48,384

44,352

20_21

98

88

49,392

44,352

21_22

98

80

49,392

40,32

22-23

95

80

47,88

40,32

23_24

93

80

46,872

40,32






[MVаr] (5)

Aholi yashash punkti uchun sutkalik reaktiv quvvat jadvali




Qishki

Yozgi

Qishgi

Yozgi

0_1

80

78

14,87838

14,50642

1_2

85

80

15,80827

14,87838

2_3

85

80

15,80827

14,87838

3_4

87

80

16,18023

14,87838

4_5

92

85

17,11013

15,80827

5_6

84

78

15,62229

14,50642

6_7

83

75

15,43631

13,94848

7_8

89

72

16,55219

13,39054

8_9

95

80

17,66807

14,87838

9_10

98

84

18,22601

15,62229

10_11

100

93

18,59797

17,29611

11_12

92

88

17,11013

16,36621

12_13

94

87

17,48209

16,18023

13_14

94

85

17,48209

15,80827

14_15

96

85

17,85405

15,80827

15_16

98

92

18,22601

17,11013

16_17

100

90

18,59797

16,73817

17_18

95

86

17,66807

15,99425

18_19

86

77

15,99425

14,32044

19_20

91

82

16,92415

15,25033

20_21

94

85

17,48209

15,80827

21_22

97

90

18,04003

16,73817

22-23

97

90

18,04003

16,73817

23_24

92

84

17,11013

15,62229










[MVar]

Neftni qazib olish uchun sutkalik reaktiv quvvat jadvali




Qishki

Yozgi

Qishgi

Yozgi

0_1

95

80

55,97792

47,1393

1_2

90

80

53,03172

47,1393

2_3

88

80

51,85323

47,1393

3_4

90

80

53,03172

47,1393

4_5

92

88

54,2102

51,85323

5_6

91

85

53,62096

50,08551

6_7

90

85

53,03172

50,08551

7_8

92

87

54,2102

51,26399

8_9

98

87

57,74565

51,26399

9_10

100

95

58,92413

55,97792

10_11

100

95

58,92413

55,97792

11_12

98

95

57,74565

55,97792

12_13

96

93

56,56716

54,79944

13_14

97

93

57,15641

54,79944

14_15

99

93

58,33489

54,79944

15_16

99

93

58,33489

54,79944

16_17

96

90

56,56716

53,03172

17_18

98

90

57,74565

53,03172

18_19

98

90

57,74565

53,03172

19_20

96

88

56,56716

51,85323

20_21

98

88

57,74565

51,85323

21_22

98

80

57,74565

47,1393

22-23

95

80

55,97792

47,1393

23_24

93

80

54,79944

47,1393








[МVА] (6)

Aholi yashash punkti uchun sutkalik to’la quvvat jadvali




Qishki

Yozgi

Qishki

Yozgi

0_1

80

78

34,13333

33,28

1_2

85

80

36,26667

34,13333

2_3

85

80

36,26667

34,13333

3_4

87

80

37,12

34,13333

4_5

92

85

39,25333

36,26667

5_6

84

78

35,84

33,28

6_7

83

75

35,41333

32

7_8

89

72

37,97333

30,72

8_9

95

80

40,53333

34,13333

9_10

98

84

41,81333

35,84

10_11

100

93

42,66667

39,68

11_12

92

88

39,25333

37,54667

12_13

94

87

40,10667

37,12

13_14

94

85

40,10667

36,26667

14_15

96

85

40,96

36,26667

15_16

98

92

41,81333

39,25333

16_17

100

90

42,66667

38,4

17_18

95

86

40,53333

36,69333

18_19

86

77

36,69333

32,85333

19_20

91

82

38,82667

34,98667

20_21

94

85

40,10667

36,26667

21_22

97

90

41,38667

38,4

22-23

97

90

41,38667

38,4

23_24

92

84

39,25333

35,84












[МVА]



Neftni qazib olish uchun sutkalik to’la quvvat jadvali




Qishki

Yozgi

Qishki

Yozgi

0_1

95

80

73,66154

62,03077

1_2

90

80

69,78462

62,03077

2_3

88

80

68,23385

62,03077

3_4

90

80

69,78462

62,03077

4_5

92

88

71,33538

68,23385

5_6

91

85

70,56

65,90769

6_7

90

85

69,78462

65,90769

7_8

92

87

71,33538

67,45846

8_9

98

87

75,98769

67,45846

9_10

100

95

77,53846

73,66154

10_11

100

95

77,53846

73,66154

11_12

98

95

75,98769

73,66154

12_13

96

93

74,43692

72,11077

13_14

97

93

75,21231

72,11077

14_15

99

93

76,76308

72,11077

15_16

99

93

76,76308

72,11077

16_17

96

90

74,43692

69,78462

17_18

98

90

75,98769

69,78462

18_19

98

90

75,98769

69,78462

19_20

96

88

74,43692

68,23385

20_21

98

88

75,98769

68,23385

21_22

98

80

75,98769

62,03077

22-23

95

80

73,66154

62,03077

23_24

93

80

72,11077

62,03077








II. KUCh TRANSFORMATORINI QUVVATI VA SONINI ANIQLASh.


Berilgan sanoat korxonalarining to‘la quvvatini 40 % -ni I –toifali, 60% - ni esa II- toifali iste'molchilar tashkil tashkil etadi.


1. I va II–toifali iste'molchilarni aktiv va to‘la quvvatlari quyidagicha aniqlanadi.
a) I – chi sanoat korxonasi uchun:
[MWt] (10)
[MWt] (11)
[MV.А] (12)
[МV.А] (13)
b) II – chi sanoat korxonasi uchun:
[МWt] (14)
[МWt] (15)
[МV.А] (16)
[МV.А] (17)
v) Umumiy to‘la quvvatni quyidagicha aniqlanadi:
[МWt] (18)
[МVаr] (19)
[МV.А] (20)

2. Agar iste'molchilarning ko‘pchilik qismi birinchi va ikkinchi toifali bo‘lsa, yoki sutkalik va yillik yuklama grafigi o‘zgarib tursa, ikki transformatorli podstantsiyadan foydalanish tavsiya qilinadi. Bunda har bir transformator umumiy yuklamaning 70% ga hisoblanadi.


Transformatorning nominal quvvatlari quyidagi shartga ko‘ra tanlanadi.

[МV.А] (21)


Ya’ni:
[МВ.А]
Demak, GOST bo‘yicha 80 MV·A; 125 MV·A va hokazo quvvatli trasformator tanlash tavsiya qilinadi.
Agar trasformatorlardan biri ishdan chiqsa, elektr ta'minoti to‘xtalmay, ikkinchisi vaqtinchalik 140 % yuklama bilan ishlashi ko‘zda tutiladi.
Iste'molchilar asosan I va II toifali bo‘lganligi uchun, uzliksiz elektr ta'minoti to‘xtamasligi uchun podstantsiyalarda ikkitadan transformator o‘rnatish tavsiya etiladi.

a) ikki hil quvvatli trasformatorlar olish ko‘zda tutiladi.


I – variant: 2 x 80 MV·A; uning o‘ta yuklanishi,

II – variant: 2 x 125 MV·A;



Ikkala variant ham normal ishlash rejimi bo‘yicha qoniqarlidir.


b) Transformatorlardan biri ishdan chiqsa, bu tanlangan variantlarni ishlashini tekshiramiz.
I – variant: 1,4· Snom.t = 1,4 · 80 = 112 MV·A;
II – variant: 1,4· Snom.t = 1,4 · 125 = 175 MV·A.
bunda, 1,4 – o‘ta yuklanish koeffitsenti.

  1. Энди иқтисодий вариантни аниқлаймиз:

I – вариант: 2 х 80 МВ·А. Типи АТДЦТН-80000/110

Uвн =115 kV; Рх =64 kVт.


Uсн=38,5 kV; Рк =365 kVт;
Uнн =6,3 kV; Iх =0,5 %; Sнн =160 МV·A


baxosi = 9 mlard so’m
II – variant: 2 x 125 MV·A. ATDTSTN-125000/110

Uвн =115 kV; Рх =105 kVт.


Uсн=38,5 kV; Рк =400 kVт;
Uнн =6,3 kV; Iх =0,55 %. Sнн = 250 МV·А

  1. Uch cho‘lg‘amli transformatorlarda reaktiv quvvatning keltirilgan isroflarini aniqlash.

I variant uchun
[kVar] (22)
[kVar] (23)


[kVar] (24)
[kVar] (25)


(26)
II variant uchun
[kVar] (22)
[kVar] (23)


[kVar] (24)
[kVar] (25)


(26)

B)transformatorning salt ishlash vaqtidagi keltirilgan isrofini aniqlash.


Ivariant uchun
(27)
II variant uchun

v) transformatorning qisqa tutashuv rejimidagi keltirilgan isrofini aniqlash
[kWt] (28)
[kWt] (29)
[kWt] (30)
II variant uchun
[kWt]
[kWt]
[kWt]
g) transformatorni o‘zidagi keltirilgan isroflarni aniqlash.
I variant uchun
(31)
(32)
II variant uchun


Bunda

d) uch cho‘lg‘amli transformator yoki avtotransformatordagi elektr energiya isrofini aniqlash.


I variant uchun
[kWt. soat] (33)
II variant uchun
[kWt. soat]
Bunda, -ВН; СН; НН cho‘lg‘amlaridagi maksimal isroflar vaqti bo‘lib, hisoblar uchun 1=2=3 teng deb qabul qilinadi.

III. TEXNIK – IQTISODIY QIYoSLASh NATIJASIDA ELEKTR STANTSIYaLARI VA PODSTANTSIYaLARINI BOSh SXEMASINI TANLASh (1 – variant uchun).


Texnik – iqtisodiy hisobni minimal keltirilgan sarf – xarajatlar bo‘yicha hisoblanadi.


I variant uchun
З = РН ·КТ + И=204 (mlrd. So’m) (34)
II variant uchun
З = РН ·КТ + И=134,75 (mlrd. So’m)
bunda, РН – normativ koeffitsent bo‘lib 0,15ga teng;
КТ – podstatsiyalarga o‘rnatilgan transformatorlarni tannarhi bo‘lib quyidagicha aniqlanadi.
I variant uchun

КТ0·nT=18 (mlrd. So’m) (35)
II variant uchun
КТ0·nT=26 (mlrd. So’m)

nTtransformatorlar soni;
К0 – bitta transformatorning tannarhi;
И –yillik ekspluatatsiya xarajatlari quyidagicha aniqlanadi (mlrd. So‘m)
I variant uchun
И = Uа.т + UЭ = 201,2 (mlrd. So’m) (36)
II variant uchun
И = Uа.т + UЭ =130,85 (mlrd. So’m)
Ua.t – amortizatsiya uchun ajratilgan sarf–xarajatlar quyidagicha hisoblanadi.
I variant uchun
Uа.т =[(Ра о)/100] Кт =1,67 (mlrd. So’m) (37)
II variant uchun
Uа.т =[(Ра о)/100] Кт=2,4 (mlrd. So’m)
bunda,
Ра – amortizatsiya uchun ajratilgan normasi 6,3 % ga teng;
Ро – podstantsiyani hizmati va ta'mirlash uchun ajratilgan xarajatlar 3 % ga teng;
UЭ – bir yillik elektr energiya isrofini narhi, mln. so‘m
I variant uchun
UЭ =  · Э=199,5 (mlrd. So’m) (38)
II variant uchun
UЭ =  · Э=128,4 (mlrd. So’m)
bunda, –1 kVat. soat elektr energiya isrofi uchun to‘lanadigan tannarhi 60 so‘m /kWt·soat

IV. QISQA TUTAShUV TOKLARNI HISOBLASh.


Qisqa tutashuv toklari asosan elektr asbob–uskuna parametrlarini tanlash yoki tekshirish, shuningdek, rele muhofazasi va avtomatika qurilmasini tanlash yoki tekshirish uchun hisoblanadi. Tarmoq elementlarining qarshiligini aniqlash uchun, odatda, hisoblash sxemasida ularning parametrlari nomlangan birliklarda, yoki nisbiy birliklarda ko‘rsatiladi.


Uch fazali qisqa tutashuv toklarini hisoblash quyidagi tartibda olib boriladi:
ko‘rilayotgan energetik tizimlar uchun hisoblash sxemasi asosida o‘rin almashtirish sxemasi tuziladi:

4.1-rasm. Oddiy tizimning hisoblash va almashtirish sxemasi.
asta–sekin o‘zgartirish yo‘li bilan o‘rin almashtirish sxemani eng sodda ko‘rinishga shunday keltiriladi, bunda natijaviy e.yu.k. ma’lum miqdor bilan xarakterlovchi manbalar guruhi yoki xar bir ta’minlovchi manba qisqa tutashuv nuqtasi bilan bitta natijaviy qarshilik XNAT orqali bog‘langan bo‘ladi.
Natijaviy qarshilikni bilgan holda Om qonuni asosida qisqa tutashuv tokining tashkil etuvchisini boshlang‘ich miqdori IPO aniqlanadi. So‘ngra zarbiy tok va zarurat tug‘ilsa, berilgan vaqt momenti t uchun qisqa tutashuv tokining davriy va boshlang‘ich tashkil etuvchisi aniqlanadi.
Tizim qarshiligi S aniqlanadi.
Tizim qarshiligi S aniqlanadi.
(39)
bu yerda –energetik tizimni nisbiy kattalikdagi qarshiligi
Liniyaning qarshiligi:
(40)
bu yerda, Xsol – liniyani solishtirma induktiv qarshiligi (6-220 kV li bir zanjirli xavo liniyasi uchun –0,4 Om/km/).
Kuch transformatorini cho‘lg‘amlaridagi qisqa tutashuv kuchlanishi quyidagicha aniqlanadi:


(41)

Kuch transformatorini cho‘lg‘amlaridagi induktiv qarshilik:


(42)
K1, K2 , K3 lar uchun natijaviy qarshiliklar quyidagicha aniqlanadi:



Paralel ishlayotgan transformatorlar uchun:

K1, K2 , K3 nuqtalariga bazis toklari aniqlanadi:
(43)
Yakunlovchi almashtirilgan sxema asosida qisqa tutashuv tokining davriy tashkil etuvchisining boshlang‘ich qiymati ( Ip.o ) aniqlanadi:
K1 nuqta uchun:

K2 nuqta uchun

K3 nuqta uchun


Shu nuqta uchun zarbiy tok

bunda, Ip.o – qisqa tutashuv tokining davriy tashkil etuvchisining boshlang‘ich qiymati;


K1 nuqta uchu
(44)
K2 nuqta uchun

K3 nuqta uchun

Ku–qisqa tutashuv tokining boshlang‘ich tashkil etuvchisining so‘nish doimiysi vaqtga bog‘liq bo‘lgan zarbiy qiymat.
Konstanta Ta va Kz o‘zaro quyidagi nisbatda bog‘langan:
Kz =(1+e-0,01/Ta) , bu 3.25 rasmda grafik ravishda ko‘rsatilgan (L.I). Ma’lum Ta bo‘yicha 3.25 rasmdagi grafikdan Ku ning tegishli qiymatini aniqlash mumkin.
Ta taxminan quyidagi ifodadan aniqlash mumkin:
(45)
bunda va – qisqa tutashuv zanjirining tegishlicha yakunlovchi induktiv va aktiv qarshiliklaridir. Odatda kurs ishisini bajarishda elektr tarmoqlarining xarakterli nuqtalari uchun 3.8 jadvalda keltirilgan T­a va Ku ning o‘rtacha qiymatlaridan foydalansa bo‘ladi.
Ku nuqta uchun qisqa tutashuv tokining boshlang‘ich tashkil etuvchisi aniqlanadi:
Aniqlash lozim bo‘lgan qisqa tutashuv toklarining hisoblanadigan vaqt τ =tcB­ + t3min ifoda orqali aniqlanadi, bunda ­ tSB­– o‘chirgichning xususiy uzish vaqti 0,05 sekunddan oshmaydi.; t3min – releli muhofazani minimal vaqti 0,01 sek.
Hisobni osonlashtirish uchun e-τ /Ta miqdorini T va Ta ning ma’lum qiymatlarida, 3.26 rasmda tasvirlangan egri chiziqlardan aniqlash maqsadga muvofiq. (A–1)
Qisqa tutashuvni to‘liq issiqlik impulsi quyidagi ifodadan aniqlanadi:
K1 nuqta uchun
(46)

K2 nuqta uchun



K3 nuqta uchun

bunda tuz – uzish vaqti.
Bk ni hisoblashda Ta doimiysini taxminiy hisoblashda 3.7, 3.8 – jadvallardan olish mumkin, elektrostansiya shinalarida qisqa tutashuv bo‘lgan holda Vk ni baholash zarur bo‘lsa, u holda qisqa tutashuv tokining yig‘indisi bo‘yicha taxminan olish mumkin.

V. ELEKTR STANSIYA VA PODSTANSIYALARDA


ASBOB – USKUNALARNI TANLASh.
Elektr apparatlari, izolyatorlar va tok o‘tkazuvchi qismlar 3 ta asosiy rejimda ishlaydi:
a) davomli ish rejimi;
b) o‘ta yuklanish rejimi, bunda K3 ning qiymati 1,4 gacha boradi;
v) qisqa tutashuv rejimi.
Davomli ish rejimida elektr apparatlarining ishonchli ishlashi, ularning nominal tok va nominal kuchlanish bo‘yicha to‘g‘ri tanlanishi bilan ta’minlanadi.
O‘ta yuklanish rejimida apparatlarni ishonchli ishlashi tok va kuchlanishlarni uzoq vaqt oshib ketishini chegaralash bilan ta’minlanadi.
Qisqa tutashuv rejimida apparatlarning ishonchli ishlashi, qisqa tutashuv toklarining elektrodinamik va termik ta’sirlar bo‘yicha asbob–uskunalarni to‘g‘ri tanlanishi bilan ta’minlanadi.
a) Ajratgich va uzgichlar quyidagicha tanlanadi:
–qurilmaning kuchlanishi bo‘yicha:

Download 244.85 Kb.

Do'stlaringiz bilan baham:
  1   2




Ma'lumotlar bazasi mualliflik huquqi bilan himoyalangan ©fayllar.org 2024
ma'muriyatiga murojaat qiling