3.4.2 MAIFI
E
: Momentary Average Interruption Event Frequency Index 
The Momentary Average Interruption Event Frequency Index (MAIFI
E
) indicates the average frequency of 
momentary interruption events. This index does not include the events immediately preceding a sustained 
interruption. Mathematically, this is given in Eq. (25). 
MAIFI
E

Served
Customers
of
Number 
Total
Events
on 
Interrupti
Momentary 
Customer 
of
Number 
Total

(25) 
To calculate the index, use Eq. (26). 
MAIFI
E

T
mi
E
N
N
IM

(26) 
3.4.3 CEMSMI
n
: Customers Experiencing Multiple Sustained Interruption and Momentary 
Interruption Events
The Customers Experiencing Multiple Sustained Interruption and Momentary Interruption Events Index 
(CEMSMI
n
) is the ratio of individual customers experiencing n or more of both sustained interruptions and 
momentary interruption events to the total customers served. Its purpose is to help identify customer issues 
that cannot be observed by using averages. Mathematically, this is given in Eq. (27). 
CEMSMI
n

Served
Customers
of
Number 
Total
ons
Interrupti
More
or 

ng
Experienci
Customers
of
Number 
Total
(27) 
To calculate the index, use Eq. (28). 
CEMSMI
n

T
N
n)
(k
CNT

(28) 
Authorized licensed use limited to: North China Electric Power University. Downloaded on February 16,2022 at 10:52:41 UTC from IEEE Xplore. Restrictions apply. 


IEEE Std 1366-2012 
IEEE Guide for Electric Power Distribution Reliability Indices 
Copyright © 2012 IEEE. All rights reserved. 
10

Download 0.52 Mb.

Do'stlaringiz bilan baham:
1   ...   13   14   15   16   17   18   19   20   ...   39




Ma'lumotlar bazasi mualliflik huquqi bilan himoyalangan ©fayllar.org 2024
ma'muriyatiga murojaat qiling