4.2. Qisqa tutashuvdan himoyani tok otsechkasi (TO) ko‘rinishida bajaramiz.
TOning ishga tushish toki
𝐼hi=𝐾z𝐼nom.kb=2,2·44,04=96,8 A
bu yerda 𝐾z=2,2 zahira koeffitsienti.
Tok relesining ishga tushish toki
𝐼ri =𝐾𝑐x𝐼hi/𝐾I=
Tok otsechkasi uchun RT-40/10 turdagi tok relesini tanlaymiz.
𝐼hi =𝐾z·𝐼hi=1,3 96,8=125,95 A
bu yerda 𝐾z=1,3 zahira koeffitsienti.
Relening ishga tushish toki
𝐼ri =𝐼hi /KI= =6,29 A
o‘ta yuklanishdan himoya uchun RT-40/6 tuodagi tok va EV-132 turdagi vaqt relesini tanlaymiz.
O‘ta yuklanishdan himoyaning hayallash vaqtini 𝑡=3𝑐 olamiz
4.4.Kuchlanish ortib ketishidan himoyaning ishga tushish kuchlanishi.
𝑈hi =1,1·𝑈kb =1,1·10,5=11,55kV=11550 V
Kuchlanish relesining ishga tushirish kuchlanishi
𝑈ri =𝑈hi /𝐾𝑈=
bu yerda 𝐾𝑈=7000/100=70 kuchlanish transformatorining transformatsiya koeffitsienti.
Kuchlanish ortib ketishini himoyasi uchun RN-53/200 turdagi kuchlanish relesini tanlaymiz.
Himoyani hayallash vaqtini 𝑡=1 minut olamiz.
MTH ning hayallash vaqti
Tanlash xususiyatini ta’minlash uchun MTH larning hayallash vaqtlari iste’molchilardan manbaga tomon yo‘nalishda ortib boradigan qilib tanlanadi.
Ikkita qo‘shma MTH larning hayallash vaqtlari orasidagi farqga vaqt pog‘onasi yoki tanlash pog‘onasi deb ataladi.
Agar MTH RT-40 turdagi elektromagnit tok relelari asosida bajarilgan bo‘lsa tanlash pog‘onasi Δ𝑡=0,5 𝑐 olinadi.
Sinxron elektrodvigatellar rele himoyasining hayallash vaqti ≈1s bo‘lganligi uchun MTH ning hayallash vaqtini
𝑡=1+0.5=1.5 𝑐. olamiz.