Power Plant Engineering


Download 3.45 Mb.
Pdf ko'rish
bet234/418
Sana17.09.2023
Hajmi3.45 Mb.
#1679900
1   ...   230   231   232   233   234   235   236   237   ...   418
Bog'liq
Power-Plant-Engineering

(B) Disadvantages
1. The part load efficiency of the open cycle plant decreases rapidly as the considerable percent-
age of power developed by the turbine is used to drive the compressor.
2. The system is sensitive to the component efficiency; particularly that of compressor. The open
cycle plant is sensitive to changes in the atmospheric air temperature, pressure and humidity.
3. The open-cycle gas turbine plant has high air rate compared to the other cycles, therefore, it
results in increased loss of heat in the exhaust gases and large diameter ductwork is necessary.
4. It is essential that the dust should be prevented from entering into the compressor in order to
minimise erosion and depositions on the blades and passages of the compressor and turbine and so
impairing their profile and efficiency. The deposition of the carbon and ash on the turbine blades is not
at all desirable as it also reduces the efficiency of the turbine.
9.2.2 CLOSED CYCLE GAS TURBINE POWER PLANT
Closed cycle gas turbine plant was originated and developed in Switzerland. In the year 1935,
J. Ackeret and C. Keller first proposed this type of machine and first plant was completed in Zurich in
1944.
It used air as working medium and had a useful output of 2 mW. Since then, a number of closed
cycle gas turbine plants have been built all over the world and largest of 17 mW capacity is at
Gelsenkirchen, Germany and has been successfully operating since 1967. In closed cycle gas turbine
plant, the working fluid (air or any other suitable gas) coming out from compressor is heated in a heater
by an external source at constant pressure. The high temperature and high-pressure air coming out from
the external heater is passed through the gas turbine. The fluid coming out from the turbine is cooled to
its original temperature in the cooler using external cooling source before passing to the compressor.
The working fluid is continuously used in the system without its change of phase and the required heat
is given to the working fluid in the heat exchanger.
The arrangement of the components of the closed cycle gas turbine plant is shown in Fig. 9.2.