- permanently allowed values of phase conductors currents
for overhead lines and
cables;
- values of nominal power, i.e. current for transformers.
3.2.2.3. It is necessary to dimensionate the entire additional equipment in o/h
line and
transformer bays in the grid 400 kV, 220 kV, 110 kV (like current instrument transformers,
disconnectors, circuit breakers and other equipment) so that it does not pose limitation to
transmission capacity
in the planned switching state, determined in accordance with the
provision 3.2.2.2, except when it is not possible to prospectively determine loads that require
dimensionation of the above mentioned equipment.