Kurs loyihasi fan : Rele himoyasi va avtomatikasi Guruhi talaba Rahbar : ass. Komolddinov S. S. Topshiriq


Download 411.46 Kb.
bet7/13
Sana23.12.2022
Hajmi411.46 Kb.
#1050121
1   2   3   4   5   6   7   8   9   10   ...   13
Bog'liq
Ollohberdi Rele kurs ishi

Qisqa tutashuv nuqtasi

K1

K2

K3

K4

Sistemadan A

50.74

46.94

3.4

53.47

Elektr dvigateldan







0,4

0,104

Maksimal tok

50.74

46.94

3.83

53.574

Minimal tok

43.9

40.83

2.98

46.51

2.2.BPP transformator himoyasi


Birlamchi ma’lumotlar:
Transformator quvvati
Yuqori kuchlanish
Past kuchlanish
2.1 Jadval №1 dan transformatorning past kuchlanish (PK) tomonidagi qisqa tutashuv tokining minimal va maksimal qiymatlarini olamiz.


Transformatorni tashqi qiska tutashuvdan himoya sifatida hayallash vaqtiga ega bo‘lmagan tok otsechkasi (bundan keyin TO) qo‘llaniladi, transformatorni ichki qisqa tutashuvdan himoya uchun differensial himoya (bundan keyin DFH), gaz himoyasi ( bundan keyin GH), yerga tutashuvdan nol ketma-ketlikdagi tok himoyasi qo‘llaniladi. Bundan tashqari, qo‘shimcha himoya sifatida o‘ta yuklanishdan maksimal tok himoyasi (bundan keyin MTH) qo‘llaniladi.
Transformatorning past kuchlanish (PK) tomonida qisqa tutashuv bo‘lganda yuqori kuchlanish (YuK) tomonidagi tok