Pursuant to Article 116 of the Energy Law
Download 0.65 Mb. Pdf ko'rish
|
Serbian Grid Code-1-43
- Bu sahifa navigatsiya:
- 4.3.8.2. Disconnecting of the generator due to voltage deviation 4.3.8.2.1.
OF THE GENERATION UNIT FROM TRANSMISSION GRID 4.3.8.1. Disconnecting of the generator due to frequency deviation 4.3.8.1.1. In accordance with the level of frequency deviation f, generation unit must be capable to stay interconnected on the transmission grid for various periods, as follows: - for frequency interval 47.5 Hz ≤ f ≤ 48 Hz, generation unit stays connected for at least 30 minutes; - for frequency interval 48.5 Hz ≤ f ≤ 49 Hz, generation unit stays connected for at least 90 minutes; - for frequency interval 49.0 Hz ≤ f ≤ 51 Hz, generation unit stays connected permanently; - for frequency interval 51 Hz ≤ f ≤ 51.5 Hz, generation unit stays connected for at least 30 minutes. 4.3.8.1.2. Reversible hydro-generation unit. i.e. pumping unit whose nominal power is above 100 MW, must be capable of prompt turn off from the transmission grid in the pumping regime for frequency range 49 Hz - 49,8 Hz. 4.3.8.1.3. Generation unit must be capable to remain interconnected to the transmission grid for the frequency change in the amount of up to ± 2 Hz/s. To change the frequency greater than ± 2 Hz/s is allowed outage generating units from the grid after 1.25 s. 4.3.8.2. Disconnecting of the generator due to voltage deviation 4.3.8.2.1. In accordance with the level of voltage deviation at the connection point on the transmission grid U m , generation unit must be capable to remain interconnected to the transmission grid for various periods, as follows: a) for connection points at 400 kV: - for frequency interval 90%U nom < U m ≤ 95%U nom , at least 60 minutes; - for frequency interval 95%U nom < U m ≤ 105%U nom , permanently; - for frequency interval 105%U nom < U m ≤ 110%U nom , at least 60 minutes; b) for connection points at 110 kV and 220kV: - for frequency interval 85%U nom < U m ≤ 90%U nom , at least 60 minutes; - for frequency interval 90%U nom < U m ≤ 110%U nom , permanently; - for frequency interval 110%U nom < U m ≤ 115%U nom , at least 60 minutes. cosφ U m [%] 43 4.3.8.2.2. In the quasi-stationary state, when the voltage at the connection point is outside the values specified in paragraph 4.3.8.2.1. generating units may be excluded from the grid by application of automatic device. Download 0.65 Mb. Do'stlaringiz bilan baham: |
Ma'lumotlar bazasi mualliflik huquqi bilan himoyalangan ©fayllar.org 2024
ma'muriyatiga murojaat qiling
ma'muriyatiga murojaat qiling