Thesis Project: Power Quality Analysis at Murdoch University eng470: Engineering Honours Thesis


Download 1.28 Mb.
Pdf ko'rish
bet6/14
Sana03.10.2023
Hajmi1.28 Mb.
#1690924
1   2   3   4   5   6   7   8   9   ...   14
Bog'liq
Abdullah2018

%
 Vo
ltage 
Unb
al
an
ce
Time of the day
Percent Voltage Unbalance
%Unbalance A
%Unbalance B
% Unbalance C
Figure 22: Percent Voltage Unbalance for all Three Phases against Time of the Day


Power Quality Analysis at Murdoch University 
45 
The percent current unbalance for each phase was plotted against time of the day as 
illustrated in Figure 24 below. 
0
50
100
150
200
250
12:00:00 AM
2:24:00 AM
4:48:00 AM
7:12:00 AM
9:36:00 AM
12:00:00 PM
2:24:00 PM
Cu
rr
e
n

M
ag
n
itu
d
e
 (
A
)
Time of the Day
Current Magnitude versus Time
Current A Magnitude
Current B Magnitude
Current C Magnitude
Figure 23: Current Magnitude versus Time
0
5
10
15
20
25
30
35
40
45
12:00:00 AM
2:24:00 AM
4:48:00 AM
7:12:00 AM
9:36:00 AM
12:00:00 PM
2:24:00 PM
%
 C
u
rr
e
n

Unb
al
an
ce
Time of the Day
Percent Current Unbalance
% Unbalance current A
% Unbalance Current B
% Unbalance Current C
Figure 24: Percent Current Unbalance for all Three Phases against Time of the Day


Power Quality Analysis at Murdoch University 
46 
The current unbalance of 42.26 % is very high and unacceptable. This may cause heating in 
the load such as in the motor or transformer winding that degrades the load. Besides, due to 
this unbalance I
2
R, losses in the cables increase, and this may lead to lower efficiency of the 
load. 
4.2 Phase Distortion 
As it can be seen from Figure 25, for voltage angle shows that there is no phase distortion 
during the duration of the measurement. All phases remain 120 electrical degrees apart 
during the entire measurement period. As a result, phase distortion is not a power quality 
issue experienced at Murdoch University. 
On the other hand, Figure 26 demonstrates the current angle for the different line currents. 
From Figure 26, it can be seen that all three phases have distortions in the current angle. The 
phase angle for Current A fluctuates between -10.2 to -41.8 electrical degrees, the angle for 
-150
-100
-50
0
50
100
150
12:00:00 AM
2:24:00 AM
4:48:00 AM
7:12:00 AM
9:36:00 AM
12:00:00 PM
2:24:00 PM

Download 1.28 Mb.

Do'stlaringiz bilan baham:
1   2   3   4   5   6   7   8   9   ...   14




Ma'lumotlar bazasi mualliflik huquqi bilan himoyalangan ©fayllar.org 2024
ma'muriyatiga murojaat qiling